Chapter 10
GFK-2843A
Jan 2020
Technical data and ordering data
64
Status indicators
One green LED (two-color LED green/red) per output
(see "Local diagnostic and status indicators" on page 12)
Diagnostic indicators
One red LED (two-color LED green/red) per output
(see "Local diagnostic and status indicators" on page 12)
WARNING
Loss of safety function
–
Connect the ground of the actuator directly to the ground terminal point of the
corresponding output on the VersaPoint connector. An external ground may not be used.
–
The connected load must not respond in a hazardous way to test pulses.
Electrical isolation/isolation of the voltage areas
Important
To provide electrical isolation between the logic level and the I/O area, it is necessary to
supply the bus coupler and this safety module from separate power supply units.
Interconnection of the power supply units in the 24 V area is not permitted. (See also
GFK-2736 user manual.)
Separate potentials in the system consisting of bus coupler/power terminal and
safety module
- Test distance
- Test voltage
5 V supply incoming remote bus/7.5 V supply (bus logic)
500 V AC, 50 Hz, 1 min.
5 V supply outgoing remote bus/7.5 V supply (bus logic)
500 V AC, 50 Hz, 1 min.
7.5 V supply (bus logic)/24 V supply U
M
, FE
500 V AC, 50 Hz, 1 min.
Approvals
For the latest approvals, please visit
https://www.emerson.com/Industrial-Automation-