User Manual
Chapter 4
GFK-2843A
Jan 2020
Assembly, removal, and electrical installation
33
Important
If the switch-off delay for stop category 1 is parameterized with a
value less than 150 ms, this value is rejected as a parameterization
error (error code 028x
hex
).
Two-channel
parameterization
Please note the following for two-channel parameterization:
Ensure that the values for the switch-off delay for stop category 1
are the same for both channels. This means that the time must
have the same value and the same value range.
5.3
Behavior of the outputs in the event of enabled
switch-off delay for stop category 1
Depending on the event that causes the outputs to be switched off, and on the
parameterization of the switch-off delay, the time until the outputs are actually switched
off can vary.
Table 10: Switching off of the outputs according to the trigger event and the
parameterization
Switch off of outputs
Influence of
parameterized
switch- off delay
Switch off of outputs
•
By the controller
Yes
Once the parameterized switch-off delay
has elapsed
•
After a bus error
Yes
Once the parameterized switch-off delay
has elapsed
•
After a short circuit, cross
circuit, failure of the supply
voltage or hardware fault
No
Immediately (only stop category 0)
•
After time monitoring has
been exceeded (watchdog
time; F
WD_Time
) (e.g., in the
event of faulty bus
connection)
Yes
Once the parameterized switch-off delay
has elapsed
WARNING
Delayed shutdown when using stop category 1
For stop category 1 please take into consideration the following:
–
The guaranteed shutdown time t
G
is extended by the parameterized switch-off delay.