Errors: messages and removal
54
Table 23: Parameterization errors
Diagnostic code
Short description
Solution
(hex)
(dec)
X21n
The parameterized
shutdown time for the
indicated output is outside
the permissible value range.
Correct value and resend
parameter data to the
module.
X210: OUT0_Ch1&2 528: OUT0_Ch1&2
X211: OUT1_Ch1&2 529: OUT1_Ch1&2
X212: OUT2_Ch1&2 530: OUT2_Ch1&2
X213: OUT3_Ch1&2 531: OUT3_Ch1&2
X22n
Outputs parameterized for
two-channel operation must
be assigned the same
shutdown times.
Correct value and resend
parameter data to the
module.
X220: OUT0_Ch1
544: OUT0_Ch1&2
X221: OUT1_Ch1
545: OUT1_Ch1&2
X222: OUT2_Ch1
546: OUT2_Ch1&2
X223: OUT3_Ch1
547: OUT3_Ch1&2
X23n
The parameterization of two
related outputs does not
correspond to the two-
channel setting.
Correct value and resend
parameter data to the
module.
X230: OUT0_Ch1&2 560: OUT0_Ch1&2
X231: OUT1_Ch1&2 561: OUT1_Ch1&2
X232: OUT2_Ch1&2 562: OUT2_Ch1&2
X233: OUT3_Ch1&2 563: OUT3_Ch1&2
X28n
The parameterized switch-
off delay time for the output
is outside the permissible
value range.
Correct value and resend
parameter data to the
module.
X280: OUT0_Ch1
640: OUT0_Ch1
X281: OUT1_Ch1
641: OUT1_Ch1
X282: OUT2_Ch1
642: OUT2_Ch1
X283: OUT3_Ch1
643: OUT3_Ch1;
X287: OUT0_Ch2
647: OUT0_Ch2
X288: OUT1_Ch2
648: OUT1_Ch2
X289: OUT2_Ch2
649: OUT2_Ch2
X28A: OUT3_Ch2
650: OUT3_Ch2
X29n
For outputs parameterized
for two- channel operation,
the same settings were not
assigned for the switch-off
delay.
Correct setting and
resend parameter data
to the module.
X290: OUT0_Ch1&2 656: OUT0_Ch1&2
X291: OUT1_Ch1&2 657: OUT1_Ch1&2
X292: OUT2_Ch1&2 658: OUT2_Ch1&2
X293: OUT3_Ch1&2 659: OUT3_Ch1&2
X2Bn
For outputs parameterized
for two- channel operation,
the same settings were not
assigned for the enable
function.
Correct setting and
resend parameter data
to the module.
X2B0: OUT0_Ch1&2 688: OUT0_Ch1&2
X2B1: OUT1_Ch1&2 689: OUT0_Ch1&2
X2B2: OUT2_Ch1&2 690: OUT0_Ch1&2
X2B3: OUT3_Ch1&2 691: OUT3_Ch1&2
X2F2
754
At least one output with
parameterized switch-off
delay is still performing a
switch-off operation.
Wait until the switch-off
operation is complete
and resend parameter
data to the module.