iCOM
Control Training and Service Manual
Temperature/Humidity Board DIP Switch #1 Settings
SW1 - 1
SW1 - 2
SW1 - 3
SW1 - 4
SW1 - 5
SW1 - 6
Comments
Off Off Off Off On Off
Internal
T/H
Sensor
On
Off
Off
Off
On
Off
Sensor A
Off On Off Off On Off Sensor
B
On
On
Off
Off
On
Off
Sensor C
Temperature/Humidity Board Jumper Settings
Jumper
Type
Setting
P2 BDM
Header
*
Open
P3
CAN Termination
*
Shunt on Pins 2 & 3
P4 Programming
*
Open
E10 – E13
Serial Port
*
Open
*
Default Setting
Jumper P3 CAN Bus Termination: The correct position of this jumper is
dependant on your environment. If the board is physically the first or last node on
the CAN Bus, the jumper needs to be shunted across pins 2 – 3 (Default position).
Otherwise position the shunt across pins 1 – 2.
Jumper P3
Jumper P4
Jumper P2
DIP Switch #1
137
Содержание Liebert iCOM
Страница 1: ...Large Systems iCOM Microprocessor Environmental Training and Service Manual TM 10098 Rev 05 27 08 ...
Страница 2: ...iCOM Control Training and Service Manual iCOM Training Service Manual 1 ...
Страница 19: ...iCOM Controls Training and Service Manual Glycool at 100 Capacity No Dead Band 18 ...
Страница 20: ...iCOM Control Training and Service Manual Glycool at 50 Capacity No Dead Band 19 ...
Страница 42: ...iCOM Control Training and Service Manual 41 ...
Страница 46: ...iCOM Control Training and Service Manual 45 ...
Страница 62: ...iCOM Control Training and Service Manual Notes 61 ...
Страница 68: ...iCOM Control Training and Service Manual Small Display Graphic View Small Display Simple View 67 ...
Страница 69: ...iCOM Controls Training and Service Manual Large Display Graphic View Large Display Simple View 68 ...
Страница 146: ...iCOM Control Training and Service Manual NOTES 145 ...
Страница 179: ...iCOM Controls Training and Service Manual Digital Scroll High Temperature Sensor Chart NTC Code S606 and S608 178 ...
Страница 203: ...iCOM Controls Training and Service Manual 202 Notes ...