iCOM
Controls Training and Service Manual
In the example below the control band begins at the 70
°
F temperature set point
and has a length of 4.5
°
F, which is ½ of the programmed temperature dead band
value plus ½ of the programmed temperature proportional band value.
As the return air temperature increases, Cooling 1 (lead compressor) is activated
at 72.5
°
F or ½ of the dead band value plus 50% of the cooling control band. If the
return air temperature continues to increase, Cooling 2 (lag compressor) will
activate at 74.5
°
F or ½ of the dead band value plus 100% of the cooling control
band.
When the return air temperature starts to decrease, Cooling 2 (lag compressor) is
deactivated at 72.5
°
F or ½ of the dead band value plus 50% of the cooling control
band and Cooling 1 (lead compressor) is deactivated at 70.5
°
F or ½ of the dead
band value plus 0% of the cooling control band.
2 Stage Compressorized Cooling – With Dead Band
Remember the temperature dead band value is used by the control to shift
the cooling on/off operations away from the temperature set point.
10
Содержание Liebert iCOM
Страница 1: ...Large Systems iCOM Microprocessor Environmental Training and Service Manual TM 10098 Rev 05 27 08 ...
Страница 2: ...iCOM Control Training and Service Manual iCOM Training Service Manual 1 ...
Страница 19: ...iCOM Controls Training and Service Manual Glycool at 100 Capacity No Dead Band 18 ...
Страница 20: ...iCOM Control Training and Service Manual Glycool at 50 Capacity No Dead Band 19 ...
Страница 42: ...iCOM Control Training and Service Manual 41 ...
Страница 46: ...iCOM Control Training and Service Manual 45 ...
Страница 62: ...iCOM Control Training and Service Manual Notes 61 ...
Страница 68: ...iCOM Control Training and Service Manual Small Display Graphic View Small Display Simple View 67 ...
Страница 69: ...iCOM Controls Training and Service Manual Large Display Graphic View Large Display Simple View 68 ...
Страница 146: ...iCOM Control Training and Service Manual NOTES 145 ...
Страница 179: ...iCOM Controls Training and Service Manual Digital Scroll High Temperature Sensor Chart NTC Code S606 and S608 178 ...
Страница 203: ...iCOM Controls Training and Service Manual 202 Notes ...