If the unit was operating in DX + FC Mode (and the FC valve is open), at the first
leaving of Phase 6 the “flow” will check (after the 600 seconds compressor off
time) if at the DT 3 (A138) checkpoint the actual unit temperature is above DT 3
(A138 see below). If true, then Freecooling will be disabled (Phase 10) for
maximum of 1 hour or until both compressors are off (Freecooling will be disabled
inside this 1 hour when 1 compressor restarts), and the compressor continues to
cycle between Phase 1, then Phase 2 and probably Phase 6. If the call for cooling
goes away, Phase 10 is reset, 1-hour timer.
Loss of Charge Protection
After Phase 1, once the pressure reaches the low pressure cut-out (single reading)
the “flow” moves to phase 8: Wait 5 minutes to reach one single reading above
Threshold 1. If OK move back to Phase 2, if NOK then move to Phase 9 and
sound Alarm (Code 3), stop compressors, leave LLSV open, no pump down; and
continue to wait a single reading to be above Threshold 1 to move to Phase 2.
This waiting phase will last forever or as long as there is a call for cooling. The
compressor may operate during the alarm is active, once the pressure conditions
allow for it.
Phases
Conditions
1
Winter Start (Low Pressure Time Delay)
2
Start of Freeze Protection (6 minutes Threshold Phase 2 ignored)
3
Freeze Protection (4 minutes of 3 minutes worth of averages)
4
Did not make Winter Start. Waiting on one reading above Threshold
Phase 1. LLSV open and compressor OFF. Five minute wait time.
5
Low Pressure Alarm (Code 1)
6
Compressor off for 10 minutes. LLSV Closed.
7
Freeze Protection Message (Code 2)
8
Off on Loss of Charge. Waiting on one reading above Threshold
Phase 1. LLSV open and compressor OFF. Five minute wait time.
9
Low Pressure Alarm (Code 3)
10
Disable Freecooling for one hour. Compressor(s) will operate during
this time.
See Flow Chart on next page.
40
Содержание Liebert iCOM
Страница 1: ...Large Systems iCOM Microprocessor Environmental Training and Service Manual TM 10098 Rev 05 27 08 ...
Страница 2: ...iCOM Control Training and Service Manual iCOM Training Service Manual 1 ...
Страница 19: ...iCOM Controls Training and Service Manual Glycool at 100 Capacity No Dead Band 18 ...
Страница 20: ...iCOM Control Training and Service Manual Glycool at 50 Capacity No Dead Band 19 ...
Страница 42: ...iCOM Control Training and Service Manual 41 ...
Страница 46: ...iCOM Control Training and Service Manual 45 ...
Страница 62: ...iCOM Control Training and Service Manual Notes 61 ...
Страница 68: ...iCOM Control Training and Service Manual Small Display Graphic View Small Display Simple View 67 ...
Страница 69: ...iCOM Controls Training and Service Manual Large Display Graphic View Large Display Simple View 68 ...
Страница 146: ...iCOM Control Training and Service Manual NOTES 145 ...
Страница 179: ...iCOM Controls Training and Service Manual Digital Scroll High Temperature Sensor Chart NTC Code S606 and S608 178 ...
Страница 203: ...iCOM Controls Training and Service Manual 202 Notes ...