iCOM
Controls Training and Service Manual
does not open, the compressor and LLSV are locked off and an alarm “Pump
Down Fail” will appear.
There is a re-pump down if the LPS opens again after the compressor has been
already stopped – a maximum of 6 re-pump-down cycles per hour are allowed: at
the 7
th
request of re-pump down the alarm “Pump Down Fail” will appear and the
compressor will be locked out.
Pump down is always performed loaded (for compressors with unloaders:
unloaders off, digital scroll: control solenoid valve disabled).
Phases
Conditions
1
Winter Start (Low Pressure Time Delay)
3
Loss of Charge
4
Did not make Winter Start. Waiting on closure of pressure
switch. LLSV open and compressor OFF. Five minute wait time.
5
Low Pressure Alarm (Code 1)
8
Off on Loss of Charge. Waiting on closure of pressure switch.
LLSV open and compressor OFF. Five minute wait time.
9
Low Pressure Alarm (Code 3)
See Flow Chart on next page.
44
Содержание Liebert iCOM
Страница 1: ...Large Systems iCOM Microprocessor Environmental Training and Service Manual TM 10098 Rev 05 27 08 ...
Страница 2: ...iCOM Control Training and Service Manual iCOM Training Service Manual 1 ...
Страница 19: ...iCOM Controls Training and Service Manual Glycool at 100 Capacity No Dead Band 18 ...
Страница 20: ...iCOM Control Training and Service Manual Glycool at 50 Capacity No Dead Band 19 ...
Страница 42: ...iCOM Control Training and Service Manual 41 ...
Страница 46: ...iCOM Control Training and Service Manual 45 ...
Страница 62: ...iCOM Control Training and Service Manual Notes 61 ...
Страница 68: ...iCOM Control Training and Service Manual Small Display Graphic View Small Display Simple View 67 ...
Страница 69: ...iCOM Controls Training and Service Manual Large Display Graphic View Large Display Simple View 68 ...
Страница 146: ...iCOM Control Training and Service Manual NOTES 145 ...
Страница 179: ...iCOM Controls Training and Service Manual Digital Scroll High Temperature Sensor Chart NTC Code S606 and S608 178 ...
Страница 203: ...iCOM Controls Training and Service Manual 202 Notes ...