iCOM
Controls Training and Service Manual
SERVICE MENU’s Continued
Set Alarm Parameters, page 1 of 7
Menu
line
Parameter
SMALL DISPLAY
(Large Display)
Default
Range
Shared
in TW1
Control
Board
Safe
S201 (Password)
-
-
-
-
S202
RTN SNSR
(Return Sensor Alarms)
YES
(Enabled)
YES, NO
(Enable, Disable)
Yes CSF
S203
HI TEMP (High Return
Temperature)
80°F
34 – 210°F
Yes
CSF
S204
LO TEMP (Low Return
Temperature)
65°F
34 – 210°F
Yes
CSF
S205
HI HUM
(High Return Humidity)
60%
1 – 99%
Yes
CSF
S206
LOW HUM
(Low Return Humidity)
40%
1 – 99%
Yes
CSF
S207
SENSOR A
(Sensor A Alarms)
NO
(Disable)
NO, YES
(Enable, Disable)
Yes CSF
S208
HI TEMPA (High
Temperature Sensor A)
90°F
34 – 210°F
Yes
CSF
S209
LO TEMPA (Low
Temperature Sensor A)
55°F
34 – 210°F
Yes
CSF
S210
HI HUM A
(High Humid Sensor A)
70%
1 – 99%
Yes
CSF
S211
LO HUM A
(Low Humid Sensor A)
30%
1 – 99%
Yes
CSF
96
Содержание Liebert iCOM
Страница 1: ...Large Systems iCOM Microprocessor Environmental Training and Service Manual TM 10098 Rev 05 27 08 ...
Страница 2: ...iCOM Control Training and Service Manual iCOM Training Service Manual 1 ...
Страница 19: ...iCOM Controls Training and Service Manual Glycool at 100 Capacity No Dead Band 18 ...
Страница 20: ...iCOM Control Training and Service Manual Glycool at 50 Capacity No Dead Band 19 ...
Страница 42: ...iCOM Control Training and Service Manual 41 ...
Страница 46: ...iCOM Control Training and Service Manual 45 ...
Страница 62: ...iCOM Control Training and Service Manual Notes 61 ...
Страница 68: ...iCOM Control Training and Service Manual Small Display Graphic View Small Display Simple View 67 ...
Страница 69: ...iCOM Controls Training and Service Manual Large Display Graphic View Large Display Simple View 68 ...
Страница 146: ...iCOM Control Training and Service Manual NOTES 145 ...
Страница 179: ...iCOM Controls Training and Service Manual Digital Scroll High Temperature Sensor Chart NTC Code S606 and S608 178 ...
Страница 203: ...iCOM Controls Training and Service Manual 202 Notes ...