Parameters
ES01
to
ES13
must be suitably configured (time band start/end and day of activation).
There are 3 settable time bands, and one or more time bands can be activated for each individual day
of the week.
Parameters
ES01
ES06
define the start and end of the 3 time bands.
ES01
Start of time band 1
00:0024:00
ES02
End of time band 1
00:0024:00
ES03
Start of time band 2
00:0024:00
ES04
End of time band 2
00:0024:00
ES05
Start of time band 3
00:0024:00
ES06
End of time band 3
00:0024:00
Parameters
ES07
ES13
define activation of the time bands in the individual days of the week.
ES07
Time bands activated for Monday
ES08
Time bands activated for Tuesday
ES09
Time bands activated for Wednesday
ES10
Time bands activated for Thursday
ES11
Time bands activated for Friday
ES12
Time bands activated for Saturday
ES13
Time bands activated for Sunday
Parameters
ES07
ES13
are made up of a pair of values that have the following meaning.
• The first value “X” represents enabling with time bands for double set point
• The second value “Y” represents enabling with time bands for automatic switching on/off from
clock
X
Y
Energy Saving time bands
ON/OFF time bands
The meanings of the values that fields “X” and “Y”
of parameters
ES07
..
ES13
:
0
= No time band enabled
1
= Time band 1 enabled
2
= Time band 2 enabled
3
= Time band 1+2 enabled
4
= Time band 3 enabled
5
= Time band 1+3 enabled
6
= Time band 2+3 enabled
7
= Time band 1+2+3 enabled
The two functions can be activated individually or both together. If the two functions overlap on the
same time band, switching off takes priority.
To disable the function, set parameters
ES01
ES06
to 00.00 or, alternatively, parameters
ES07
ES13
to
00.