IC200CX EVO
user manual
9
3
The unit can be switched ON and OFF in several ways:
• From digital input configured as remote ON/OFF
• From the keyboard
• From time bands
• From remote supervision/XWeb
3.1 ON/OFF by digital input
The ON/OFF digital input has priority over the keyboard. The unit can be switched ON and OFF from
keyboard only if the unit is in ON mode by the input (contact closed).
If you do not intend to use the remote ON/OFF function via digital input, identify the relevant
terminals in the wiring diagram and jumper them (terminals 12).
Warning: the ON/OFF input is in no case intended as an thermoregulation input, i.e.
it should not be connected to external control units or thermostats used for
temperature control. For this use it is advisable to act on the
Energy saving
contact
(see below).
The typical use of the ON / OFF contact is to turn the unit on and off in predefined
periods by means of external mechanical clocks or relay devices controlled by SMS.
With the contact inactive (no
bridge in the terminal board)
the unit is switched off, the
display shows OFF.
With active contact (bridge in
terminal block) the unit is
enabled in the last selected
operating mode (see below).
ON/OFF
UNIT ON/OFF