Appendix A: Recommended Refrigerant Gas Alarm Settings • A-77
Appendix A: Recommended Refrigerant Gas
Alarm Settings
Gas
Alarm Settings (PPM)
Leak
Spill
Evacuate
CO
2
/R-744
1500
2000
3000
FA188
100
300
500
FC72
100
300
500
H1301
100
300
500
H1211
100
300
500
H2402
100
300
500
H1234YF
100
300
500
HFP
100
300
500
N1230
100
300
500
NH
3
/R-717
50
150
300
R-11
100
300
500
R-12
100
300
500
R-21
100
300
500
R-22
100
300
500
R-23
100
300
500
R-32
100
300
500
R-113
100
300
500
R-114
100
300
500
R-123
25
35
50
R-124
100
300
500
R-125
100
300
500
R-134A
100
300
500
R-227
100
300
500
R-236FA
100
300
500
R-245FA
100
300
500
R-401A
100
300
500
R-402A
100
300
500
R-402B
100
300
500
R-404A
100
300
500
R-407A
100
300
500
R-408A
100
300
500
R-407C
100
300
500
Table 10-2
- Recommended Alarm Settings and Gas Enumeration