Supervisory Controller Setup for RLDS RLDS Setup on REFLECS, E2, Einstein, and Supervisory Controllers • 69
11.4.2. Edit Application
1. Once the RLDS has been added, click the
application name to view parameters.
11.4.3. General
1. Set up the RLDS Application by going to the
General
tab.
2. Click
Edit
button to configure the parameters.
3. Set the
Number of Zones
.
11.4.4. Zone Setup
1. Click
Zone Setup
tab.
2. Set the
Refrigerant Type
.
11.4.5. Zone Alarms Leak/Spill/Evac
1. Click
Zone Alms Leak
,
Zone Alms Spill
, and
Zone Alms Evac
tab to configure the setpoints.
2. Set the Leak/Spill/Evac setpoint for each zone:
Default values are Leak = 100, Spill = 300, and
Evac = 500.
Figure 11-6
- Edit RLDS Application in the Supervisory
Controller
Figure 11-7
- RLDS Application General Tab
Figure 11-8
- RLDS Zone Setup Tab
Figure 11-9
- RLDS Zone Alarms