75 • RLDS I&O Manual
026-1309 Rev 11
5. Scroll to the “MORE” option and press
ENTER
. Note that “MORE” will flash when it is selected.
6. Scroll to and select the “IR DIGIPOT” option (see below) and press
ENTER
.
7. Use the UP and DOWN arrows to adjust the MW reading to 450 (or as close as possible). When at the
proper value, press ESC once.
8. Scroll to “DET DIGIPOT” option (see above) and press ENTER.
9. Use the UP and DOWN arrows to adjust the IR VOLT reading to 4.20 (or as close as possible). When at
the proper value, press ESC once.
10.Press
ESC
to save.
11.Press
ESC
to get to the System Menu. Scroll to Service Mode and press ENTER twice to leave Service
Mode. Press ESC once and allow the instrument to complete a pressure check and purge cycle
(approximately 2 minutes).
If the faults cannot be cleared using the above procedure, call the factory for further assistance.
Figure 12-1
- Sample DIGIPOT Readings
IMPORTANT: If IR VOLT does not reach 4.200 ±0.100 volts when adjusting the DIGIPOT, return to step 6
to lower the IR emitter setting. If the IR emitter setting is 450 ±20 mW, adjust the new IR emitter setting to
375 ±20 mW. Repeat step 8 with the new IR emitter setting.