66 • RLDS I&O Manual
026-1309 Rev 11
11 RLDS Setup on
REFLECS, E2,
Einstein, and
Supervisory
Controllers
Dip switch 8 on the Gateway should be set to the OFF
position for E2, Einstein, Supervisory controllers, and
set to the ON position for REFLECS controllers.
11.1. REFLECS Setup for RLDS
Set dip switch 8 to ON and follow the steps for setting
up RLDS units through the REFLECS controller
interface:
1. Log on.
2. Press 7 for
Configuration
to reach the
CONFIGURATION
screen.
Input Definitions should be set here to show how the
sensor control is linked to the zone. The number of
devices and RLDS units are connected to the
Gateway and enabled is the number of address slots
the Gateway will use.
3. Press 1 for
Input Definitions
to reach the
INPUT DEFINITIONS
screen.
4. Pressing the down arrow several times will get
you to the input list of
SENS01-48
.
Bd
(board)
is the address of the Gateway,
Pt
(point) is the
zone and allows you to define where the sensor
input comes from.
The board number for the RLDS setup is the
address of the Gateway. If there are three or less
RLDS controllers connected to a Gateway, the
Gateway address = the RLDS address. However, if
there are more than three RLDS controllers, the
second Gateway address will be the one entered for
the board number, but the RLDS controllers are set 1
to 3 on the second Gateway.
5. Press 0 (zero) to go back to the
CONFIGURATION
screen.
6. Press 7 for
I/O Brd Setup
to reach the
I/O
BOARD MENU
screen.
7. Press 2 to
Set Device
#’s
.
The Gateway will react as three 16AI boards. The
number of RLDS controllers plus the real number of
16AIs = the total number of 16AIs to enter in the next
step:
8. At the
I/O BOARD DEVICE NUMBERS
screen, press the down arrow key to reach
Number 16AI Boards
and enter the number of
how many 16AI boards and RLDS controllers
there are. Press Enter.
9. Arrow down to the
I/O BOARD
MENU
and
press 0 (zero) twice to go back to the
MAIN
MENU
screen.
10. Press 4 for
Sensor Control
.
11. Press 2 for
Setup
--up to 48 sensor control
programs are allowed. Select one of the 48
units and press Enter to reach the
SENSOR
SETUP
screen.
12. Press the right arrow to move to the
Name
field to change the name, and press the down or
right arrow to move to the (sensor)
Type
field.
Use the “.” and “
—
” keys to scroll through the
options and select
IRLDS
.
13. Use the arrow keys to move off the active
fields and press 0 (zero) twice to go back to the
main screen.
11.2. E2 Version 3.01 and below
Setup for RLDS (without
Gateway)
Set dip switch 8 to OFF and follow the steps for
setting up RLDS units through the E2 controller
interface
1. Log in to the E2 with Level 4 access.
2. Press
-
Connected I/O Boards
Содержание GW-810-3760
Страница 1: ...Refrigerant Leak Detection System RLDS Installation and Operation Manual 026 1309 Rev 11 ...
Страница 37: ...30 RLDS I O Manual 026 1309 Rev 11 Figure 4 22 Connecting the Gateway to the RS485 Network ...
Страница 84: ...Appendix B System Menu Map B 79 Appendix B System Menu Map ...
Страница 85: ...B 80 RLDS I O Manual 026 1309 Rev 11 ...