S600+ Instruction Manual
Revised July-2017
I/O
4-21
Figure 4-26. Digital Output Schematic (24 V Switched Indicator)
Table 4-17. DIGOUT Pin Connections for SKT-E
Pin
Function
36
DIGOUT-CH1
37
DIGOUT-CH2
Table 4-18. DIGOUT Pin Connections for SKT-F
Pin
Function
37
DIGOUT-CH3
36
DIGOUT-CH4
35
RETURN CH1-4
34
DIGOUT-CH5
33
DIGOUT-CH6
32
DIGOUT-CH7
31
DIGOUT-CH8
30
RETURN CH5-8
29
DIGOUT-CH9
28
DIGOUT-CH10
27
DIGOUT-CH11
26
DIGOUT-CH12
25
RETURN CH9-12
4.2.3 Turbine Pulse Inputs
You can use the four pulse inputs either independently or as two pairs.
Generally, they are used for dual pulse measurement, such as turbine
applications. In dual pulse mode, you can enable level A or B pulse
checking.
Each input has an input range of 1 Hz to 10 kHz. Each channel has live
integrity checking. If cabling faults develop or if the pre-amp power
fails, the system activates a circuit fail alarm.
Table 4-19
shows the dual-pulse input pin connections. Refer to
Figure
4-27
for field wiring schematics.
Содержание FloBoss S600+
Страница 55: ...S600 Instruction Manual Revised July 2017 I O 4 17 Figure 4 20 Prover Module P154 Figure 4 21 Prover Module ...
Страница 66: ...S600 Instruction Manual 4 28 I O Revised July 2017 This page is intentionally left blank ...
Страница 84: ...S600 Instruction Manual 5 18 Front Panel Revised July 2017 This page is intentionally left blank ...
Страница 92: ...S600 Instruction Manual 6 8 Webserver Access Revised July 2017 This page is intentionally left blank ...
Страница 114: ...S600 Instruction Manual A 8 Glossary Revised July 2017 This page is intentionally left blank ...
Страница 122: ...S600 Instruction Manual B 8 Front Panel Navigation Revised July 2017 This page is intentionally left blank ...
Страница 150: ...S600 Instruction Manual C 28 Chromatographs Revised July 2017 2350 USA 2551 USA ...