S600+ Instruction Manual
C-6
Chromatographs
Revised July-2017
Raw Mole %s
Updated from a successful telemetry poll
Raw CV (etc.)
Updated from a successful telemetry poll
Latest Mole %s
Adjusted/normalised from latest report
Last Good Mole %
Adjusted/normalised from latest report
Raw Alarms Register
Detailed indication of global alarms
Codes Request Flag
Trigger for Modbus master telemetry module
Component Codes
Updates from a successful telemetry poll
Last Good Set of Mole
%s
S600+-internally ordered from last good raw
set
Time Stamp
Time of the last good analysis
C.3 Configuration Type: Keypad Mole Percentage Set Only
Use this configuration when there is no chromatograph linked to the
S600+. The keypad set describes the entire mole percentage
breakdown, including additionals and C6+ entries. Thus, whenever you
use the keypad set, the system ignores the entries from the other arrays
for additionals and C6+ and uses the keypad set alone.
Processing of the keypad set and its subsequent copying into the in-use
set depends on the acceptance type:
Accept and Copy
The sum of the keypad components is regularly maintained. When the
Accept command is issued:
If range checking is
enabled,
the keypad set is checked against
individual mole percentage low and high limits.
If range checking is
disabled,
the keypad sum is checked for the
range 99.9 to 100.1.
If the keypad set is
valid,
the system copies it to the in-use set.
If the keypad set is
invalid
, an alarm is raised and the in-use set
remains intact.
Accept, Normalise, and
Copy
The sum of the keypad components is regularly maintained. When the
Accept command is issued:
If range checking is
enabled,
the keypad set is checked against
individual mole percentage low and high limits.
If range checking is
disabled,
the keypad sum is checked for the
range 99.9 to 100.1.
If the keypad set is
valid,
the system normalises it and then copies
it to the in-use set
If the keypad set is
invalid
, an alarm is raised and the in-use set
remains intact.
Auto Normalise
The sum of the keypad components is regularly maintained. On a
regular basis:
If range checking is
enabled,
the keypad set is checked against
individual mole percentage low and high limits.
If range checking is
disabled,
the keypad sum is checked for the
range 99.9 to 100.1.
Содержание FloBoss S600+
Страница 55: ...S600 Instruction Manual Revised July 2017 I O 4 17 Figure 4 20 Prover Module P154 Figure 4 21 Prover Module ...
Страница 66: ...S600 Instruction Manual 4 28 I O Revised July 2017 This page is intentionally left blank ...
Страница 84: ...S600 Instruction Manual 5 18 Front Panel Revised July 2017 This page is intentionally left blank ...
Страница 92: ...S600 Instruction Manual 6 8 Webserver Access Revised July 2017 This page is intentionally left blank ...
Страница 114: ...S600 Instruction Manual A 8 Glossary Revised July 2017 This page is intentionally left blank ...
Страница 122: ...S600 Instruction Manual B 8 Front Panel Navigation Revised July 2017 This page is intentionally left blank ...
Страница 150: ...S600 Instruction Manual C 28 Chromatographs Revised July 2017 2350 USA 2551 USA ...