S600+ Instruction Manual
Revised July-2017
Troubleshooting
8-3
Note
:
The LED is orange while at the Startup menu. If it is still
orange when the configuration is running, contact your local
sales representative or technical support.
8.2.5 I/O LED
If the red or green LEDs on the backplate of the I/O module do not
blink while the S600+ is operating:
Check the I/O module connections. Power down, remove and
reseat the I/O module, and then re-apply power.
Check the front panel display and LED. If they are not lit, you may
have a power issue.
Check with the person who configured the unit whether you have
the correct I/O module fitted.
Check the running configuration for any BAD TX or BAD RX
messages. From the Main menu, select
TECH/ENGINEER
>
COMMUNICATIONS
>
SERIAL PORTS
>
PORT 08
.
8.2.6 I/O Fail Messages
If the front panel displays an
I/O Fail
message:
Check the jumper settings on the I/O modules.
Check the I/O field wiring connections.
Check that the I/O modules are seated and secured.
8.2.7 Serial Communications
If you are experiencing troubles with a serial communications
connection (RS-232, RS-422, or RS-485):
Check to make sure power is applied to the S600+.
Check the wiring to the termination block or connector. Refer to
Chapter 3
,
CPU
.
Check the communication port settings from the front panel
display.
Check the Modbus address.
Check the setting of the termination resistor jumper.
8.3
Procedures
Initiate a cold start after you send a new configuration to the S600+ or
to recover from extreme situations, such as a corrupted database. A
cold start builds a new metering database, using the configuration data
stored in the S600+’s flash memory.
Note
:
You
must
perform a cold start if you update or otherwise
change the firmware.
Содержание FloBoss S600+
Страница 55: ...S600 Instruction Manual Revised July 2017 I O 4 17 Figure 4 20 Prover Module P154 Figure 4 21 Prover Module ...
Страница 66: ...S600 Instruction Manual 4 28 I O Revised July 2017 This page is intentionally left blank ...
Страница 84: ...S600 Instruction Manual 5 18 Front Panel Revised July 2017 This page is intentionally left blank ...
Страница 92: ...S600 Instruction Manual 6 8 Webserver Access Revised July 2017 This page is intentionally left blank ...
Страница 114: ...S600 Instruction Manual A 8 Glossary Revised July 2017 This page is intentionally left blank ...
Страница 122: ...S600 Instruction Manual B 8 Front Panel Navigation Revised July 2017 This page is intentionally left blank ...
Страница 150: ...S600 Instruction Manual C 28 Chromatographs Revised July 2017 2350 USA 2551 USA ...