S600+ Instruction Manual
C-10
Chromatographs
Revised July-2017
Stage
Description
15
Wait for Status Data Reply
(3)
Wait up to the time-out period for the
2551 to respond. If no reply has been
received, then set the telemetry fail
alarm and set the stage to
Idle
.
If a reply
has
been received
and
the new
report available flag is still set
and
the
report stream still matches the S600+
cycle stream, then set the stage to Pre-
reset Delay (1). Otherwise, set the next
stage to Idle (since the chromatograph is
now out-of-step with the S600+).
16
Pre-reset Delay (1)
Delay, then set the flag for the Modbus
master process to reset the new data
flag at data address 3058. Set the next
stage to
Wait for Reset Reponse
.
17
Wait for Reset Response
Wait up to the time-out period for the
2551 to respond. If no reply has been
received, then set the telemetry fail
alarm and set the stage to
Idle
.
If a reply
has
been received, then set the
next stage to Idle. This is the last stage
of the normal data acquisition cycle.
18
Delay after Report (Non-
Matching)
Wait up to the specified time, then set
the flag for the Modbus master to poll for
status data at data addresses 3041 to
3061.
19
Wait for Status Data Reply
(4)
Wait up to the time-out period for the
2551 to respond. If no reply has been
received, then set the telemetry fail
alarm and set the stage to
Idle
.
If a reply
has
been received
and
the new
report available flag is still set
and
the
report stream
does not
match the
S600+ cycle stream, then set the stage
to
Pre-reset Delay (2)
. Otherwise, set
the next stage to
Idle
(since the
chromatograph is now out-of-step with
the S600+, most probably because
another S600+ has reset the new data
flag).
20
Pre-reset Delay (2)
Delay, then set the flag for the Modbus
master process to reset the new data
flag at data address 3058. Set the next
stage to
Wait for Reset Response (2)
.
21
Wait for Reset Response
(2)
Wait up to the time-out period for the
2551 to respond. If no reply has been
received, then set the telemetry fail
alarm and set the stage to
Idle
.
If a reply
has
been received, then set the
next stage to Idle. This is the last stage
of the cycle where a new report has
been flagged by is not assigned to this
S600+.
Содержание FloBoss S600+
Страница 55: ...S600 Instruction Manual Revised July 2017 I O 4 17 Figure 4 20 Prover Module P154 Figure 4 21 Prover Module ...
Страница 66: ...S600 Instruction Manual 4 28 I O Revised July 2017 This page is intentionally left blank ...
Страница 84: ...S600 Instruction Manual 5 18 Front Panel Revised July 2017 This page is intentionally left blank ...
Страница 92: ...S600 Instruction Manual 6 8 Webserver Access Revised July 2017 This page is intentionally left blank ...
Страница 114: ...S600 Instruction Manual A 8 Glossary Revised July 2017 This page is intentionally left blank ...
Страница 122: ...S600 Instruction Manual B 8 Front Panel Navigation Revised July 2017 This page is intentionally left blank ...
Страница 150: ...S600 Instruction Manual C 28 Chromatographs Revised July 2017 2350 USA 2551 USA ...