1. Decrease remote set point pressure to the lower range limit.
2. Loosen the adjustment screw on link A (key 116) and adjust the length so the set point indicator points to the lower
limit of the process scale. Tighten the screw.
3. Make fine zero adjustments by loosening the zero adjustment locking screw (key 102) and turning the zero
adjustment screw (key 108). Tighten the locking screw (key 102). Refer to figure 3‐2 for location of the screws.
4. Increase the remote set point pressure to the upper range limit.
5. To increase the span, proceed as follows:
a. Turn the span adjustment screw clockwise.
b. To increase the span further than the adjustment allows, move both ends of link A (key 116) to the right.
c. Make fine adjustments with the span adjustment screw.
6. To decrease the span, proceed as follows:
a. Turn the span adjustment screw counterclockwise.
b. To decrease the span further than the adjustment allows, move both ends of link A (key 116) to the left.
c. Make fine adjustments with the span adjustment screw.
7. Repeat the adjustments until the upper and lower indications are aligned with the 0 and 100 percent markings on
the process scale.
8. Adjust the remote set point pressure to 50 percent of the remote set point range.
9. The remote set point indicator should be accurate to within
±
2 percent of the process scale span. If the accuracy is
outside
±
2 percent of the process scale span, proceed to the following linearity adjustment procedure.
10. Adjust the set point indicator to 50
±
1 percent of the process scale range by loosening the zero adjustment locking
screw and turning the zero adjustment screw. Tighten the locking screw.
11. Adjust the remote set point pressure to the upper and lower limits of the remote set point range and make sure the
set point indicator is still within
±
1 percent at the 0 percent and at the 100 percent process scale marks.
12. Perform the appropriate flapper alignment procedure and, if necessary, the process pointer zero‐and‐span
calibration procedure in Section 3 or 4.
Remote Set Point Linearity Adjustment
Adjust the linearity by loosening and repositioning the linearity adjustment screw in the curved slot on the lever arm of
pivot assembly B (key 115). Adjusting the linearity affects the zero‐and‐span adjustment.
1. Adjust the remote set point pressure to 50 percent of the remote set point range. The set point indicator should
indicate the 50
±
1 percent mark on the scale. If not, make fine adjustments by loosening the zero adjustment
locking screw and turning the zero adjustment screw.
2. Adjust the remote set point pressure to 0 percent and note the indicator position relative to the process scale 0
percent marking.
3. Adjust the remote set point pressure to 100 percent and note the indicator position relative to the process scale
100 percent marking.
4. If the greatest misalignment is positive (the set point indicator is to the right of the process scale markings), loosen
the linearity screw and move it clockwise in the slot. If the misalignment is negative, move the linearity screw
counterclockwise in the slot.
5. If misalignment is greater than 1 percent of the process scale span at the 0 and 100 percent markings, with one
positive and the other negative, perform the remote set point zero‐and‐span adjustment procedure to correct a
span error.