Instruction Manual
D200156X012
4194HA, HB, HC Controllers
July 2018
62
Note
Before starting the following procedure, remove the controller from the case. Perform steps 1 through 7 of the Replacing the
Differential Pressure Unit procedure. Then, perform steps 1 and 2 of the Replacing the Case and Cover procedure.
1. Perform the procedures required in the Note above.
2. Remove the two machine screws (key 71) on the side of the rate/reset valve assembly (key 262).
3. Gently pull the rate tubing assembly away from the rate/reset assembly and, remove the gasket (key 5) from the
side of the rate/reset assembly.
4. Remove the nut holding the reset tubing assembly (key 43) into the rate/reset valve assembly.
5. Remove the nut holding the proportional tubing assembly (key 40) into the rate/reset assembly.
6. Remove the nut holding the relief tubing assembly (key 44, option F only) into the rate/reset assembly.
7. While holding the rate/reset valve assembly, remove the machine screw (key 162) from the frame.
8. Remove the rate/reset valve assembly from the frame.
9. Inspect and, if necessary, replace the gasket (key 5).
10. To install the replacement rate/reset valve assembly, insert the assembly into its position on the frame (key 3).
11. Insert the valve assembly mounting screw (key 162) into the valve assembly and tighten.
12. Insert the gasket (key 5) and hold it in place while installing the two machine screws (key 71) holding the rate
tubing assembly (key 137) to the valve assembly and tighten the screws.
13. Insert the reset tubing assembly (key 43) into the rate/reset valve assembly and tighten the nut.
14. Insert the proportional tubing assembly (key 40) into the rate/reset valve assembly and tighten the nut.
15. Insert the relief tubing assembly (key 44, option F only) into the rate/reset valve assembly and tighten the nut.
16. Turn the reset to 0.01 and the rate valve to OFF.
17. Apply the proper supply pressure to the controller, drive the controller output to within
±
0.14 bar (2 psig) of the
supply pressure by capping the nozzle and check the tubing connections for leaks.
18. Install the controller assembly in the case and cover.
Replacing the Differential Relief Valve Assembly (suffix letter F)
Refer to the 4194HB or 4194HC option F portion of figure 6‐1 for key number locations.
1. Loosen the two mounting screws in the differential relief valve (key 55) and remove the relief valve.
2. Inspect the O‐rings on the replacement relief valve. Apply a suitable lubricant to the O‐rings.
3. Install the replacement relief valve into the controller frame, keeping in mind that:
D
When the arrow points up, the valve relieves with decreasing output pressure.
D
When the arrow points down, the valve relieves with increasing output pressure.
4. Tighten the two screws holding the relief valve to the frame.
5. The relief valve differential pressure is factory‐set at 0.3 bar (5 psig). Maximum pressure differential is 0.5 bar (7
psig); minimum pressure differential is 0.14 bar (2 psig). If a different differential pressure setting is desired, refer to
the anti‐reset windup valve calibration procedure in this manual.
Replacing the Relief Valve Tubing Assembly (suffix letter F)
Note
Before starting the following procedure, remove the controller from the case. Perform steps 1 through 7 of the Replacing the
Differential Pressure Unit procedure. Then, perform steps 1 and 2 of the Replacing the Case and Cover procedure.