Instruction Manual
D200156X012
4194HA, HB, HC Controllers
July 2018
23
The white portion of the adjustment produces direct controller action. The black portion produces reverse controller
action.
After changing the action, tighten the screws on the proportional band indicator cover.
Reset (suffix letter B) Adjustment
Locate the reset adjustment. Rotate the adjustment clockwise to decrease the minutes per repeat or counterclockwise
to increase the minutes per repeat. Increasing the minutes per repeat provides a slower reset action.
Rate (suffix letter C) Adjustment
Locate the rate adjustment. Rotate the adjustment clockwise to decrease the minutes (faster rate action) or
counterclockwise to increase the minutes (slower rate action).
Anti‐Reset Windup (suffix letter F) Adjustment
If the arrow on the relief valve points toward the top of the controller case, as shown in figure 3‐1, the valve opens
when output pressure falls. If the arrow points in the opposite direction, the valve opens when output pressure rises.
Turn the adjusting screw counterclockwise to increase differential relief pressure; clockwise to decrease it. Differential
relief pressure is factory set at 0.3 bar (5 psi). Maximum differential relief pressure is 0.5 bar (7 psi). The minimum is 0.1
bar (2 psi).
Switching the Auto/Manual Station (suffix letter E)
Note
Switching the controller between automatic and manual mode without balancing can disturb the process and cause controller
cycling.
Refer to figure 6‐5 if the controller has the auto/manual station option.
Two balance methods are used to equalize the manual output pressure with the controller output pressure. To switch
from automatic to manual mode, carefully adjust the loader knob until the metal ball inside the plastic tube moves
into the switching zone. Then move the automatic/manual switch to MANUAL. Turn the loader knob clockwise to
increase the controller output or counterclockwise to decrease it.
To switch from manual to automatic mode, slide the set point indicator to move the ball into the switching zone. Turn
the switch to AUTO and move the set point indicator to control the output.
When the automatic/manual switch is in AUTO, adjusting the loader knob has no effect on the controller output.
When the automatic/manual switch is in MANUAL, changing the set point adjustment has no effect on the controller
output.
Prestartup Checks for 4194HB and HC Controllers
Refer to figure 3‐1 for location of adjustments and to figure 6‐1 for location of key numbers.