DL8000 Preset Instruction Manual
E-84
DL8000 Keypad Display
Revised February-2016
14/03/12 12:26:02
Test AO Ch
Use AI Ch
AO current val(EU)
AI current val(EU)
Set AO current val
AO ch 1
AI ch 1
10.000000
9.911288
( STOP to End )
Note
:
If you are using an external resource for analog input, the system
displays
only
the AO current value and replaces the AI current
value with the message
Check Ext Load
:
14/03/12 12:26:02
Test AO Ch
Use AI Ch
AO current val(EU)
<Check Ext Load >
Set AO current val
AO ch 1
NONE
( STOP to End )
In this case, you enter an AO current value and check the externally
connected load.
14/03/12 12:26:02
Test AO Ch
Use AI Ch
AO current val(EU)
<Check Ext Load >
Set AO current val
AO ch 1
NONE
11
( STOP to End )
Press
STOP
to end the test for the current channel and select a new
channel to test.
Point Fail
Alarm
When you select an AO module for diagnostics, the system checks for
point fail alarms. If a point fail alarm occurs, the program prompts you
to exit the diagnostic process.
14/03/12 12:26:02
Point Fail Alarm
EXIT To Go Back
When you press
EXIT
, the Select Channel screen redisplays. If there is
no point alarm, you can select a channel and continue with the
diagnostic process.