DL8000 Preset Instruction Manual
D-24
Communications Protocols
Revised February-2016
Stop Batch
[0x0F]
Stops a batch which is in progress and is not stopped. This simulates
pressing
Stop
on the DL8000 preset.
The
Stop
key [63,0,61] action determines the manner in which the batch
stops:
If no active alarm with more than info severity is present and batch
remaining quantity [63,0,3] is less than minimum preset quantity [63,0,27]
then batch ends.
If Stop key action is Low Flow (0), the system waits for flow rate to
become zero before starting pump stop delay timer for closing the pump.
If Stop key action is Immediate (1), then batch is stopped immediately and
no pump stop delay used.
The DL8000 sets a flag to indicate that the batch has stopped (and is
restartable).
Flags Immediately Set
Batch Stopped (if batch gets stopped)
or
Batch Ended (if batch is ended)
Flags Immediately
Cleared
None
Exceptions
No batch in progress
Manual operating mode
Supporting
Parameters
Stop key action [63,0,61]
Results
If the batch halts then the DL8000 displays “Batch
Halt” and “Start to Load” messages. If the batch
has completed then the DL8000 displays “Batch
Completed” and “Please Wait” messages. In both
conditions, the DL8000 waits for the next
command from the TAS.