1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
127/192
Reset
If the probe value of the high discharge temperature is lower than “AL39 -
AL40 (differential)”
Restart
Automatic. Manual when there are AL41 per hour (Reset procedure in Menu
function).
Symbol
On the display the symbol
is blinking
Action
Alarm Relay and buzzer on
Compressor involved
OFF
C1HP - C2HP - C3HP - C4HP- C5HP
– C6HP compressor high pressure alarms
Label on alarm
visualization menu
C1HP
( compressor 1 high pressure alarm)
– …
C6HP
(compressor 6 high
pressure alarm)
Origin
The unit is running and the digital input of the compressor high pressure switch
is active
Reset
Digital input not active
Restart
Reset procedure in Menu function
Reset procedure in Menu function
Always manual AL54 = 0
Always automatic AL54 =16
From manual to utomatic if AL54 value is between 1 and 15
Symbol
On the display the symbol
is blinking
Action
Alarm Relay + and buzzer on
Regulation
Condensing fan
If FA02=0 the fan is forced at maximum speed for 60 seconds then switched
off
If FA02=1 the fan is forced at maximum speed for 60 seconds then regulate
according to normal fan regulation
C1Mn - C2Mn - C3Mn - C4Mn
– C5Mn – C6Mn -Compressor maintenance
Label on alarm
visualization menu
C1Mn
(Compressor 1 maintenance)
–…
C6Mn
(Compressor 6 maintenance)
Origin
Compressor running hours > Hour counter setpoint
Reset
Hour reset in function menu
Restart
Manual
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Regulation
Action
Only display warning messages
Loads
Not changed
C1oP - C2oP - C3oP - C4oP - - C5oP
– C6oP Pressure switch alarm / compressor oil
Label on alarm
visualization menu
C1oP
(Compressor 1pressure switch …
C6oP
(Compressor 6 pressure switch)
Origin
The alarm is not signalled: during the AL01 delay after turning on the
compressor, during the AL12 delay that starts after the AL11 delay when the
unit is properly running
Reset
Digital input not active
Restart
Automatic - Manual after AL013 events per hour (Reset procedure in Menu
function).
If AL76=1 the alarm is only a warning and the compressor remains on
Symbol
On the display the symbol
is blinking
Action
Alarm Relay + and buzzer on
Содержание Dixell iChill IC200D EVO Series
Страница 1: ...IC200D EVO rel firmware 4 3 ...
Страница 42: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 42 192 Auxiliary output status ...
Страница 177: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 177 192 VI622 or TI620 led keyboard ...
Страница 180: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 180 192 Not used ...
Страница 182: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 182 192 ...