1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
130/192
47.
ALARMS LIST
47.1 MACHINE ALARMS
Alarm
Code
Alarm description
Comp.
Anti freeze
heaters
Boiler
Support
heaters
Evaporator
Pump /
Supply fan
Condenser
Pump
Domestic
hot water
Water
pump
Solar
panel
Water
pump
Ventilaz.
cond.
Cir1 Cir2
Auxiliary
relay
ACF1
...
AC13
Configuration alarm
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ACFL
Condenser flow alarm
OFF
OFF
(3)
OFF
AEE
Eeprom alarm
OFF
OFF
OFF
OFF
OFF
AEFL
Evaporator flow alarm
OFF
OFF (boiler)
OFF
(3)
OFF
AEht
High water temperature inlat
evaporator
OFF
AEUn
Unloading signalling from high
temp. of evaporator water
AHFL
Domestic hot water flow switch
alarm
OFF
(6)
OFF
OFF
ALC1
General alarm
OFF
OFF
OFF
OFF
OFF
OFF
ALC2
Genearl alarm type 2
OFF
(3)
OFF
(3)
OFF
(3)
OFF
(3)
OFF
(3)
OFF
(3)
ALOC
Generic alarm
OFF
OFF
OFF
OFF
OFF
ALSF
Phase sequence alarm
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ALti
Low air temperature of the
evaporator inlet (air / air unit)
Alarm
ALti
Low evaporator inlet temperature
in air/air unit
AP1
...
AP8
Probe alarm
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
APE1
...
APE8
I/O Expansion probe alarm
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
APFL
Solar panel flow switch alarm
OFF
(6)
OFF
OFF
APr1
APr2
Remote keyboard probe alarm
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
OFF
(1)
Содержание Dixell iChill IC200D EVO Series
Страница 1: ...IC200D EVO rel firmware 4 3 ...
Страница 42: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 42 192 Auxiliary output status ...
Страница 177: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 177 192 VI622 or TI620 led keyboard ...
Страница 180: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 180 192 Not used ...
Страница 182: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 182 192 ...