1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
120/192
ASUn Solar panel water pump mintenance
Label on alarm
visualization menu
ASUn
(Domestic hot water pump maintenance)
Origin
Pump running hours > Hour counter setpoint
Reset
Hour reset in function menu
Restart
Manual
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Regulation
Action
Only display warning messages
Loads
Not changed
AtAS Domestic hot water pump overload alarm
Label on alarm
visualization menu
AtAS
(domestic hot water pump overload)
Origin
Digital input active
Reset
Digital input not active
Restart
Automatic reset if number of alarms per hour < AL75.
Manual reset if number of alarms per hour = AL75 (reset procedure in function
menu).
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
Domestic hot water pump OFF
AtC1 - AtC2 Condenser pump overload alarm
Label on alarm
visualization menu
AtC1
(overload pump alarm of condenser 1)
AtC2
(overload pump alarm of support condenser 2)
Origin
Active ID when it is configured as overload pump of condenser 1
Active ID when it is configured as overload pump of condenser 2.
Reset
With active digital input
Restart
Manual (reset procedure in function menu).
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
Condenser water pump and compressors OFF
AtE1 - AtE2 Evaporator pump overload alarm
Label on alarm
visualization menu
AtE1
(overload pump alarm of evaporator 1)
AtE2
(overload pump alarm of support evaporator 2)
Origin
Active ID when it is configured as overload pump of evaporator 1
Active ID when it is configured as overload pump of support evaporator 2.
Reset
With active digital input
Restart
Manual (reset procedure in function menu).
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
Evaporator water pump and compressors OFF
AtHS Domestic hot water heaters overload alarm
Label on alarm
visualization menu
AtHS
(domestic hot water heaters overload)
Origin
Digital input active
Содержание Dixell iChill IC200D EVO Series
Страница 1: ...IC200D EVO rel firmware 4 3 ...
Страница 42: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 42 192 Auxiliary output status ...
Страница 177: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 177 192 VI622 or TI620 led keyboard ...
Страница 180: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 180 192 Not used ...
Страница 182: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 182 192 ...