1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
13/192
TI620
5.
FIRST INSTALLING
5.1 ON BOARD CLOCK (OPTIONAL)
If giving power supply the
bottom display shows “
rtC
” alternated with a temperature or pressure value, It is
necessary to set the internal clock.
After a power failure, clock back-up battery lasts maximum 3 or 4 days. After this period it is necessary to set
the clock again.
The internal clock is an option and it is not possible to update the instrument; it is necessary to order
the instrument already complete of this features.
5.2 REAL TIME CLOCK SETUP
1. Push
MENU
key for some seconds until the bottom display shows
“Hour
” and the top display shows its
value.
2. Push
SET
one time: the value is blinking
3. Use the Up and Down keys to adjust it. Push
SET
one time to confirm; automatically the display shows
next parameter
4. Repeat the operations 2. 3. and 4. for all the RTC parameters:
-
Min:
minutes
(0÷60)
-
UdAy:
day of the week
(Sun
= Sunday,
Mon
=Monday,
tuE
=Tuesday,
UEd
= Wednesday,
tHu
=
Thursday,
Fri
=Friday,
SAt
=Saturday)
-
dAy:
day of the month (0÷31)
-
MntH:
month (1÷12)
-
yEAr:
year (00÷99)
6.
PARAMETER PROGRAMMING
6.1 PROGRAMMING
WITH THE “HOT KEY 64”
Download: how to program an instrument with a programmed “Hot Key”
6.1.1
1.
Power off the instrument
2.
Insert the hot key already programmed (by software Wizmate or other instrument)
3.
Power on the instrument
4.
Automatically the parameters are downloaded
During the download the regulation is locked and the top display shows the “
doL
” blinking label. At the end
of the download will appear:
“End”
if the programming procedure is completely OK, after 30seconds the regulation starts automatically.
“Err”
if the programming procedure has found an error and the parameter have not been transferred. In this
case turn off and then on the instrument supply to repeat the operation or remove the hot key, with power
supply off, to restart the regulation.
Uploa
d: How to program a “Hot Key” with the parameters of the instrument
6.1.2
1. Power on the instrument
2. Insert the hot key
3.
Enter the function Menu
Содержание Dixell iChill IC200D EVO Series
Страница 1: ...IC200D EVO rel firmware 4 3 ...
Страница 42: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 42 192 Auxiliary output status ...
Страница 177: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 177 192 VI622 or TI620 led keyboard ...
Страница 180: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 180 192 Not used ...
Страница 182: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 182 192 ...