1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
153/192
CO 47
Unloading Differential. From temperature / pressure in HP mode (See
unloading function).
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
CO 48
Maximum unloading duration time from temperature/pressure control.
1
250
Min
CO 49
Number of steps for circuit with active unloading
1= 1st step
2= 2nd step
3= 3rd step
1
3
CO 50
Minimum ON time of the capacity step after the unloading function start (only
for capacity compressor)
0
250
Sec
CO 51
Setpoint of the solenoid valve (on) of the liquid injection
0
32
150
302
°C
°F
Dec / int
int
CO 52
Setpoint of the solenoid valve (off) of the liquid injection
0.1
0
25.0
45
°C
°F
Dec
int
CO 53
Maximum time of work in neutral zone without insert resource
0
250
Min
10 Min
CO 54
Maximum time of work in neutral zone without rotation resource
0
999
Hr
1Hr
CO 55
Set point unloading compressor from low evaporator water temperature
-50.0
-58
110.0
230
°C
°F
Dec
int
CO 56
Differential unloading compressor from low evaporator water temperature
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
CO 57
Maximum unloading duration time from low evaporator water temperature
0
250
Min
CO 58
maximum time pump-down in stopped
CO58 = 0 Not enabled
0
250
Sec
CO 59
maximum time pump-down in started
CO59 = 0 Not enabled
0
250
Sec
CO 60
Maximum time start up compressor inverter controlled
0
250
sec
CO 61
Minimum value proportional output from start up compressor
0
100
%
CO 62
Minimum time capacity variation from start up compressor inverter controlled
0
250
sec
CO 63
Minimum percentage continuative of work of the compressor inverter
controlled before to start counting CO64 time
0
100
%
CO 64
Maximum time continuative of work of the compressor with percentage less of
CO63
0
250
Min
10 Min
CO 65
Time of forcing the compressor inverter controlled to the maximum power
0
250
sec
sec
CO 66
Maximum time continuative of work of the compressor inverter controlled
0
999
Hr
1Hr
CO 67
Minimum value of the compressor 1 inverter controlled
1
CO68
%
CO 68
Maximum value of the compressor 1 inverter controlled
CO67
100
%
CO 69
Minimum value of the compressor 2 inverter controlled
1
CO70
%
CO 70
Maximum value of the compressor 2 inverter controlled
CO69
100
%
CO 71
Minimum time capacity variation compressor inverter controlled
1
250
sec
CO 72
Maximum operating time of a single compressor
0
250
Min
CO 73
Domestic hot water pump hour counter
0
999
10 Hr
10 Hr
CO 74
Solar panel water pump hour counter
0
999
10 Hr
10 Hr
CO 75
Forced time to reverse the 4 way valve when the compressor is switched off
0
250
sec
CO 76
Maximum number of compressors to use in Chiller
1
15
CO 77
Maximum number of compressors to use in Heat pump
1
15
CO 78
Maximum number of compressors to use in Domestic hot water
1
15
CO 79
Maximum % output of the inverter compressor in Chiller
1
100
%
CO 80
Maximum % output of the inverter compressor in Heat pump
1
100
%
CO 81
Maximum % output of the inverter compressor in Domestic hot water
1
100
%
CO 82
Outside temperature to reduce inverter compressor speed in Heat pump
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
CO 83
Hysteresis temperature to reduce inverter compressor speed in Heat pump
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
CO 84
Compressor speed if outside temperature > CO82
0
100
%
CO 85
Evaporator water pump OFF time if the set point is reached
0
250
10 min
CO 86
Evaporator water pump OFF time if the machine is STD-BY or OFF
0
250
10 Ore
CO 87
Evaporator water pump ON time
0
250
Sec
10sec
CO 88
Condenser water pump OFF time if the set point is reached
0
250
10 min
CO 89
Condenser water pump OFF time if the machine is STD-BY or OFF
0
250
10 Ore
CO 90
Condenser water pump ON time
0
250
Sec
10sec
Содержание Dixell iChill IC200D EVO Series
Страница 1: ...IC200D EVO rel firmware 4 3 ...
Страница 42: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 42 192 Auxiliary output status ...
Страница 177: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 177 192 VI622 or TI620 led keyboard ...
Страница 180: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 180 192 Not used ...
Страница 182: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 182 192 ...