1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
159/192
Ar 8
Thermoregulation probe for anti-freeze / condenser heaters.
0= not enabled.
1= Condenser common water inlet probe.
2= Condenser common water inlet and condenser inlet 1 / 2 probe.
3= Condenser water outlet 1 / 2 probe.
4= Condenser water outlet 1 / 2 and common outlet
5= External temperature
0
5
Ar 9
Anti-freeze heaters or condenser/evaporator water pump control with unit in
remote OFF or stand-by mode:
0= Control not enable
1=Controlled by anti-freeze thermoregulation.
0
1
Ar 10
Anti-freeze heaters control for condenser/evaporator faulty probe:
0= Anti-freeze heaters OFF
1= Anti-freeze heaters ON
0
1
Ar 11
Boiler function
0=Not enabled
1=Enabled for integration heating
2= Enabled for heating
0
2
Ar 12
External air temperaure setpoint for boiler heaters (on)
-50.0
-58
110.0
230
°C
°F
Dec
int
Ar 13
Temperature differential for boiler heaters (off)
0.1
0
25.0
45
°C
°F
Dec
int
Ar 14
Time delay before turning the boiler on
0
250
Min
Ar 15
Setpoint for boiler heaters (on) in chiller
-50.0
-58
110.0
230
°C
°F
Dec
int
Ar 16
Proportional band for boiler heaters in chiller
0.1
0
25.0
45
°C
°F
Dec
int
Ar 17
Setpoint for boiler heaters (on) in HP
-50.0
-58
110.0
230
°C
°F
Dec
int
Ar 18
Proportional band for boiler heaters in HP
0.1
0
25.0
45
°C
°F
Dec
int
Ar 19
External air setpoint to stop the compressor as integration function
-50.0
-58
110.0
230
°C
°F
Dec
int
Ar 20
External air differential to stop the compressor as integration function
0.1
0
25.0
45
°C
°F
Dec
int
Ar21
Termoregulation probe anti freeze alarm in chiller mode
0= Not enabled
1= Evaporator inlet
2= Evaporator outlet 1 and 2
3= Evaporator outlet 1 and 2 and common outlet
4= External temperature
0
4
Ar22
Termoregulation probe anti freeze alarm in heat pump mode
0= Not enabled
1= Evaporator inlet
2= Evaporator outlet 1 and 2
3= Evaporator outlet 1 and 2 and common outlet
4= External temperature
0
4
Ar23
Termoregulation probe anti freeze alarm water condenser
0= not enabled.
1= Condenser common water inlet probe.
2= Condenser common water inlet and condenser inlet 1 / 2 probe.
3= Condenser water outlet 1 / 2 probe.
4= Condenser water outlet 1 / 2 and common outlet
5= External temperature
0
5
Ar24
Water pump / antifreeze alarm in OFF/ stand-by
0= Aways in OFF
1= ON only with thermoregulation control
0
1
Ar25
Termoregulation probe water pump in antifreeze mode
0= Not enabled
1= Evaporator inlet
2= Evaporator outlet 1 and 2
3= Evaporator outlet 1 and 2 and common outlet
4= External temperature
0
4
Ar26
Set point starting water pump in antifreeze alarm
-50.0
-58
110.0
230
°C
°F
Dec
int
Ar27
Differential starting water pump in antifreeze alarm
0.1
0
25.0
45
°C
°F
Dec
int
Resistenze condensatore
Ar28
Set point condenser antifreeze heaters in chiller
-50.0
-58
110.0
230
°C
°F
Dec
int
Ar29
Differential condenser antifreeze heaters in chiller
0.1
0
25.0
45
°C
°F
Dec
int
Ar30
Set point condenser antifreeze heaters in heat pump
-50.0
-58
110.0
230
°C
°F
Dec
int
Ar31
Differential condenser antifreeze heaters in heat pump
0.1
0
25.0
45
°C
°F
Dec
int
Содержание Dixell iChill IC200D EVO Series
Страница 1: ...IC200D EVO rel firmware 4 3 ...
Страница 42: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 42 192 Auxiliary output status ...
Страница 177: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 177 192 VI622 or TI620 led keyboard ...
Страница 180: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 180 192 Not used ...
Страница 182: ...1592015610 User manual IC200D EVO GB rel1 0 10 11 2015_rev10 IC200D 182 192 ...