18
C6.2.38/0719/E
Figure 15: Power cable molded plug (IP65)
Figure 16: Connecting the molded plug power cable to the connection pins
4.2.3 Assembly of the molded plug cable
▪
Make sure to use only R290 qualified and dedicated molded plug power cables with grounding
connection and retainer.
▪
Check that the O-ring on the molded plug connector is in place and not damaged.
▪
Shut off power supply.
▪
Check that the circle fence is clean and dry before connecting the molded plug power cable.
▪
Connect the grounding of the molded plug power cable to the compressor circle fence.
▪
Attach the molded plug connector to the compressor connection pins. Smoothly push the molded
plug connector by hand as far as possible towards the pins. Never use a tool to knock the molded
plug as this could damage the glass inserts of the pins
▪
Secure the connection with the retainer.
4.2.4 Removing the molded plug power cable
▪
Shut off power supply.
▪
Remove the retainer from the connection.
▪
Remove the molded plug connector from the connection pins.
▪
Disconnect the grounding from the compressor circle fence.
NOTE: To select the appropriate molded plug power cables, please refer to the Emerson spare
parts software available at