47
ADVANCED USER GUIDE
IP66/Nema 4X variable speed drive
MENU 4: CURRENT AND TORQUE CONTROL
CONTROL TECHNIQUES
3854 en - 03.2008 / b
6 - MENU 4: CURRENT AND TORQUE CONTROL
6.1 - List of parameters in Menu 4
Parameter
Name
Type
Adjustment range
Factory setting
User
setting
4.01
Current magnitude
RO/P
0 to max. current
-
-
drive (A)
4.02
Active current
RO/P
± max. drive current
-
-
4.03
Not used
4.04
Current demand
RO/P
± active current limit
-
-
(% active In)
4.05
Not used
and
4.06
4.07
Symmetrical current limit
R-W
0 to + 300.0% (% active In)
165.0%
4.08
Torque reference
R-W
± 300.0% (% active In)
0
4.09
Not used
and
4.10
4.11
Torque mode selector
R-W
0 or 1
0
4.12
Current demand filter
R-W
0 to 10 ms
0
4.13
Current loop proportional gain
R-W
0 to 999
20
4.14
Current loop integral gain
R-W
0 to 250
40
4.15
Thermal time constant
R-W
0 to 250 s
89 s
4.16
Thermal protection mode
R-W
0 or 1
0
4.17
Reactive current
RO/P
± 9999
-
-
4.18
Overriding current limit
RO/P
0 to + 300% (% active In)
-
-
4.19
Overload accumulator
RO/P
0 to 100.0%
-
-
4.20
Percentage load
RO/P
± active current limit
-
-
(% active In)
4.21
Selection of load display
R-W
0 or 1
0
4.22
Not used
to
4.51
4.52
Max. speed in torque control mode
R-W
0 to 32000 rpm
1500 rpm