ADVANCED USER GUIDE
IP66/Nema 4X variable speed drive
MENU 16: PLC FUNCTIONS
CONTROL TECHNIQUES
3854 en - 03.2008 / b
: Counter power-up status
Adjustment range : 0 or 1
Factory setting
: 0
0 (Prev. val.) (Prec): On power-up, the counter takes the
value it had before power-down.
1 (Reset to 0) (0): On power-up, the counter takes the value
of
16.85
.
: Counter enable source
Adjustment range :
0.00
to
21.51
Factory setting
:
0.00
Used to select the internal bit which enables upcounting or
downcounting. While this input is not enabled, pulses on the
upcount and downcount inputs are not taken into account.
Only "bit" type parameters can be programmed. If an
unsuitable parameter is addressed, the input will be frozen
at 0.
: Counter initialisation
Adjustment range : 0 or 1
Factory setting
: 0
0 (Disabled) (OFF): Inactive.
1 (Enabled) (On): Causes initialisation of the counter to the
initial value.
: Counter output destination
Adjustment range :
0.00
to
21.51
Factory setting
:
0.00
Determines the internal parameter which will be assigned by
the counter output.
Only "bit" type parameters can be programmed.
If an unsuitable parameter is assigned, the output is not sent
to any address.
16.86
16.87
16.88
16.89