14 . 

Select °F or °C Readout

 – Changes the display readout 

to Celsius or Fahrenheit as required .

15 . 

Select Audio Prompting (Beeper) On or Off

 – Factory  

default setting is 

b, On

 . If you wish to turn off the beeper 

select OFF .

16 . 

Select Daylight Saving Time Calculation 

– This feature 

will allow the thermostat to calculate the DST automati-
cally and apply it to the Real Time Clock display . Default 
is On . 

17 & 18 .

 Select Automatic Schedule

 – This feature allows  

programming a “Comfort Temperature” into all program 
periods with the 

Auto Schedule

 key . When 

Heat AS

 

(for Heat mode) or 

Cool AS

 (for Cool mode) is selected

 

On

, the Auto Schedule feature is ready to be set . 

Off

 

indicates that the feature is not ready to be used or a 
“Comfort Temperature" is already set . See Auto Schedule 
in Programming section .

19 & 20 . 

Select Cool Savings™

 – Cool Savings™ provides 

an energy saving temperature offset (from 1-6 degrees) 
under peak cooling load conditions (high outdoor tem-
peratures) . If selected on, Cool Savings™ becomes active 
when the air-conditioner runs for periods of longer than 20 
minutes . When active, Cool Savings™ gradually offsets the 
indoor temperature display downward . The first 1° of adjust-
ment will take one hour of continuous air conditioner run 
time with subsequent 1° adjustments occurring with each 
additional half hour of run time (Example: For a 2° offset, 
the air conditioner would need to run continuously for 1 ½ 
hours) . The offset is limited to the number of degrees you 
select from 1 up to 6 . When an offset starts or is active, 
“Cool Savings” will flash on the display .

 

The principle of this energy saving feature takes advantage 
of the long air conditioning run times lowering the indoor 
humidity allowing a slightly higher temperature to feel 
comfortable . As the peak load subsides, this feature also 
takes advantage of the air conditioner's increased capacity 
under more efficient conditions to gradually reduce the off-
set back to zero and return control to the selected setpoint 
temperature .

 

If Cool Savings is selected off, no temperature offset will

 occur .
21 .  

Compressor Optimization

 – (Not available on earlier 

models) CO provides a delay in circulator fan operation 
after the compressor tuns on or off . With CO selected ON, 
when the compressor turns on (for a call for heat in heat 
pump or a call for cool) the fan will be delayed for five 
seconds before turning on to allow the air to be heated or 
cooled . After the compressor turns off for call for cool, the 
fan will continue to run for 20 seconds to capture addi-
tional cooling from the system . If CO is set to OFF, there 
will be no delay in fan operation .

22 . 

Heat Temperature Limit Range

 – This feature adjusts 

the highest setpoint temperature for heat . The default 
setting is 99°F . It can be changed to a setting between 
62°F and 98°F .

 Temperature Limit" 

icon will be displayed 

to the left of your setpoint temperature when using this 
feature . 

"Temperature Limit" 

icon will flash if an attempt 

is made to adjust the temperature beyond the range 
selected .

23 . 

Cool Temperature Limit Range

 – This feature adjusts  

the lowest setpoint temperature for cool . The default  
setting is 45°F . It can be changed to a setting between 
46°F and 82°F . 

"Temperature Limit" 

icon will be dis-

played to the left of your setpoint temperature when using 
this feature . 

"Temperature Limit" 

icon will flash if an 

attempt is made to adjust the temperature beyond the 
range selected .

24 & 25 . 

Keypad Lockout

 – This step allows you to select 

the type of lockout or limited range security required . If no  
lockout or limited range security is required, press 

 to  

advance the menu .

 

Three security settings are available in this menu item . 
Use the   or   keys to select the lockout desired . 
Lockout selections are:

 

"Keypad Lockout 

and

 L"

 = Total Lockout . Total Lockout 

locks all keys .

 

"Keypad Lockout

 and 

P"

 = Partial Lockout . Partial Lock-

out allows only the 

 or 

 keys to operate within your 

set temperature limits .

 

"Temperature Limit/Keypad Lockout"

 prevents chang-

ing the temperature limits in the Configuration Menu .

 

After the type of lockout is selected, press 

 . 

 

Keypad Lockout Combination Number Selection 

 

Display will read 

"000" "Keypad Lockout"

 .

 

Skip this step and continue through the remainder of the 
configuration menu if you require an Air Filter Change 
out indicator or Humidifier Pad Change out indicator by 
pressing the 

 key to advance .

 

Return to this point when you are ready to start your  
selected lock-out and continue by:

 

 Pressing 

 or   keys to select your keypad lockout 

combination number . Note: 

"000"

 is not a valid combina-

tion choice .

 

Record the number you select for future use.

 Press  to exit the menu . The security feature you select 

will start in 10 seconds . The system key will remain active 
for 10 seconds to allow setting Heat, Off, Cool or Auto .

 

To unlock the keypad, press Menu, then press Installer 
Config . Display will show 

"000"

 and keypad lock . Enter 

the code used to lock the keypad and press 

 .

26 & 27 .

 Select Fast Second Stage, ON or OFF – 

Selecting 

FA ON forces additional heat stages to come on quickly 
when 

 is used to raise the temperature a few degrees 

above the room . Select this setting if you want the heat to 
increase quickly when you manually raise the tempera-
ture .

 

Selecting FA OFF allows the thermostat to calculate an 
optimal time to bring on additional stages of heat . When 
the 

 is used to raise the setting above the room tem-

perature additional heat stages may come on very quickly 
or very slowly (up to 30 minutes later) depending on 
recent system performance . Select this setting if you do 
not require the additional heat stages to come on quickly 
when you manually raise the setting and want to allow the 
thermostat to stage based on recent system performance .

INSTALLER/CONFIGURATION MENU

7

Содержание 1F95-1280

Страница 1: ... Thermostat Configuration Options Thermostat Applications Maximum Stages Heat Cool W Economizer Max Stage Heat Cool Single Stage 1 No Heat Pump SS1 Gas Oil Electric Heat Only Cool Only or Heat Cool Systems 2 or 3 wire Hydronic Zone Hot Water or Steam Systems 24 Volt or Millivolt 1 1 1 2 Multi Stage 2 No Heat Pump MS2 2 2 2 3 Heat Pump 1 Single Stage Compressor Heat Pump HP1 Single Stage Compressor...

Страница 2: ...he Power Stealing Switches Fig 1 should be left in the On position for most systems The information in the following table details the thermostat power method and switch options WARNING Thermostat installation and all components of the control system shall conform to Class II circuits per the NEC code INSTALLATION Figure 1 Thermostat Base Multi Stage 1F95 1280 2 AA Batteries Power Stealing Switche...

Страница 3: ...gured for Electric Heat Installer Configuration Menu selects O or B for changeover function Set to O terminal energized in Cool mode Set to B terminal energized in Heat emergency mode Power closed connection for SPDT 3 wire zone valve Fault or system malfunction indicator for Heat Pumps with L terminal connection COOLING CLASS II TRANSFORMER HOT 24VAC NEUTRAL 120VAC HEATING 120VAC Dual fuel option...

Страница 4: ...2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 2 9 3 0 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 3 19 2 1 11 10 15 16 9 8 17 13 12 4 18 14 A steady Cool Savings display indicates the feature is enabled in the installer menu A flashing Cool Savings display indicates the feature is active 15 Remote indicates that the indoor remote temperature sensor is being accessed Outdoor Remote indi cates the outdoor remote temperat...

Страница 5: ...s Continuous Display backlight 12 LO dL HI Selects Backlight Intensity 13 0 Temperature 5 LO to 5 HI Selects Adjustable Ambient Temperature Display range 5 LO to 5 HI 14 F C Selects F C Display temperature units in Fahrenheit or Celsius 15 On b OFF Selects audible Beeper On Off 16 On dS OFF Selects Daylight Saving Time calculation 17 On Heat AS OFF Selects Automatic Schedule for comfort temperatur...

Страница 6: ...ctory default setting is fast cycle FA Cr in all modes Heat Cool Emer To change to slow cycling SL Cr press touch keys or toggle between FA SL The cycle rates are below Mode Fast rate Slow rate Heat SS1 MS2 0 6 F 1 5 F Cool SS1 MS2 1 2 F 1 7 F Heat Pump HP1 HP2 1 2 F 1 7 F Emer Heat HP1 HP2 0 6 F 1 7 F 10 Select Compressor Lockout CL Selecting CL On will cause the thermostat to wait 5 minutes betw...

Страница 7: ...tting between 62 F and 98 F Temperature Limit icon will be displayed to the left of your setpoint temperature when using this feature Temperature Limit icon will flash if an attempt is made to adjust the temperature beyond the range selected 23 Cool Temperature Limit Range This feature adjusts the lowest setpoint temperature for cool The default setting is 45 F It can be changed to a setting betwe...

Страница 8: ...eat will not turn on The default setting is 60 but can be set in the range of 5 to 79 INSTALLER CONFIGURATION MENU If indoor temperature drops below 45 because of a pos sible heat pump malfunction the thermostat will turn off the pump and switch to Auxiliary heat Call for Service will display on screen There are two ways the thermostat will return to normal heat pump operation Press any key to ret...

Страница 9: ...below room tempera ture The heating system should stop operating Cooling 1 Press SYSTEM to select COOL 2 Press to adjust the thermostat setting below room tem perature The blower should come on immediately on high speed followed by cold air circulation The display should show System On If the setpoint temperature display is flashing the compressor lockout feature is operating see Configuration men...

Страница 10: ...inutes only in clock display 4 Press and hold either the or touch keys until you reach the correct minutes 5 Press Set Time once again to display year 6 Press either the or touch key until you reach the correct year 7 Press Set Time once again to display month 8 Press either the or touch key until you reach the correct month 9 Press Set Time once again to display date of the month along with day o...

Страница 11: ...gram all the heating temperatures during the day to a comfortable temperature and then lower the temperature 6 at night Auto Schedule Cool will program all of the cooling time periods to the same temperature Note Auto Schedule is available only when the thermostat is first powered on after the thermostat has been reset or anytime you turn AS on in the Configuration Menu item 18 AS Heat or 19 AS Co...

Страница 12: ...cil in your own program times and temperatures The 1F95 1280 comes configured for 7 day programming and can also be configured for 5 1 1 programming see configura tion section Factory settings are listed on Monday Saturday and Sunday If you are re programming a 5 1 1 day schedule pencil in your own times and temperatures directly below the factory times and temperatures If you are re programming a...

Страница 13: ...ration of the thermostat the current tempera ture displayed will be the weighted average of the local sensor and the remote sensor using the formula local sensor weight x local sensor temperature remote sensor weight x remote sensor temperature local sensor weight remote sensor weight Example Local sensor temperature is 80 and the remote sensor is 70 If weight is selected H4 the averaged temperatu...

Страница 14: ...stem operates correctly replace the thermostat Thermostat Setting Thermostat Thermometer Disagree 1 Thermostat thermometer setting requires adjustment The thermometer can be adjusted 4 degrees See Temperature Display Adjustment in the Configuration Menu section Furnace Air Conditioner Cycles Too Fast or Too Slow narrow or wide temperature swing 1 The location of the thermostat and or the size of t...

Страница 15: ...15 NOTES ...

Страница 16: ...White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co Homeowner Help Line 1 800 284 2925 www white rodgers com www emersonclimate com ...

Отзывы: