background image

INSTALLER/CONFIGURATION MENU

1 .  This control can be configured for:
 

MS2

 – Multi-Stage System - No Heat Pump (2 heat/2 

cool)

 

HP1

 – Heat Pump with one stage of compressor (2 

heat/1 cool)

 

HP2

 – Heat Pump with two stage compressor or two

 

compressor system, Gas or Electric backup; (Dual Fuel

 

see menu item 27) (4 heat/2 cool)

 

SS1

 – Single Stage System and 3 wire zone systems see 

wiring diagrams .

2 . 

GAS or Electric (ELE)

 fan operation . If the heating 

system requires the thermostat to energize the fan, select 
ELE . Select GAS if the heating system energizes the 
fan on a call for heat . 

Note: Resetting the thermostat 

switches the option to GAS.

3 . 

O/B Terminal selection

 – Selects the operation of the 

reversing valve (when item 1 is set to HP1 or HP2 only) .  
 When set to "O" the changeover valve will be energized  
 in COOL to accommodate the majority of heat applica-
tions . If the heat pump requires the changeover valve to  
 energize in HEAT, select "B" .

4 . 

Programs per week 

– This control can be configured for 

7 independent day or 5/1/1 day programming or nonpro-
grammable modes . Default is 7-day mode . The display 
indicates

 "7 Days"

 as default . Other options 

"5 Days"

 or 

"0 Days"

 can be selected . If 

"0 Days" 

is selected for non-

programmable mode, the step for EMR will be skipped, as 
this feature will not be available in this mode .

5 . 

System Switch Configuration (MS2/SS1) 

– This ther-

mostat is configured for Heat and Cool with Auto change-
over default (Cool-Off-Heat-Auto) . It can be configured as 
Heat & Cool (Cool-Off-Heat), or Heat Only (Off-Heat), or 
Cool Only (Cool-Off) .

 

When the control is in heat pump configuration 

(HP1/

 HP2)

, the system switch configuration will have an 

 

additional mode available, 

Em

 for Emergency Mode .

6 . 

Energy Management Recovery (EMR)

 – (this step is 

skipped if configured as non-programmable) . When set 
to "On" causes the thermostat to start heating or cooling 
early to make the building temperature reach the program 
setpoint at the time you specify . 

 

Example:

 The heating program is 65°F at night and 70° 

at 7 AM . If the building temperature is 65°F, the difference 
is 5°F . Allowing 5 minutes per °F rise, the thermostat set-
point will change to 70° at 6:35 AM . Cooling allows more 
time per °F, because it takes longer to reach temperature .

7, 8 & 9 . 

Cycle Rate Selection

 – The factory default setting  

is fast cycle (FA Cr) in all modes (Heat, Cool, Emer) . To 
change to slow cycling (SL, Cr), press touch keys   or 

 toggle between FA & SL . The cycle rates are below:

 

Mode 

Fast rate 

Slow rate

 

Heat (SS1, MS2) 

   0 .6°F 

   1 .5°F

 

Cool (SS1, MS2) 

   1 .2°F 

   1 .7°F

 

Heat Pump (HP1, HP2)      1 .2°F 

   1 .7°F

 

Emer Heat (HP1, HP2) 

   0 .6°F 

   1 .7°F

10 . 

Select Compressor Lockout (CL)

 – Selecting (CL On) 

will cause the thermostat to wait 5 minutes between cool-
ing cycles . This is intended to help protect the compressor 
from short cycling . Some of the newer compressors have 
a time delay built in and do not require this feature to be 
activated in the thermostat . Your compressor manufactur-
er can tell you if this lockout feature is already present in 
their system . When the thermostat compressor time delay 
is activated, it will flash the set point for up to five minutes .

11 . 

Select Continuous Backlight (dL)

 – In low lighting con-

ditions, display backlight improves the display contrast . 
When 

C

 terminal is connected, selecting dL On will turn  

the backlight on continuously . Selecting dL Off will turn 
the backlight on momentarily after any key is pressed .  
When 

C

 terminal is not powered (battery only), dL On  

enables the momentary backlight whenever a key is 
pressed . 

12 . 

Select Backlight Intensity

 – This thermostat has the  

ability to provide two selectable intensities of the back-
light: HI and LO . You can toggle the selection between HI 
and LO .

13 . 

Select Temperature Display Adjustment 5 LO to 5 HI

 

This allows you to adjust the room temperature display 
by -5°F to +5°F in 1° steps . Your thermostat was accu-
rately calibrated at the factory, however you have the 
option to change the display temperature value to match 
the previous thermostat, if you so prefer .

CONFIGURATION MENU

Screen

Reference

Number

SS1

MS2

HP1
HP2 

Press 

key

Displayed 

Factory 

(Default)

Press 

 or 

 

to select from 

listed options

Comments

34

(60) Cd

0-99

Selects compressor off delay in seconds, dF selected On

35

(80) AO

-5 - 79

Selects Auxiliary Heat cut out temperature . This item appears if HP1 

or HP2 is selected and outdoor sensor is installed and enabled .

36

(0) PP

1, 2, 3

Selects Pre-occupancy purge . Not available if 4 is 0

37

(OFF) EC

On

Selects Economizer or Damper Operation (default) . Not available if 4 

is 0

41

(OFF) Change 

UV Lamp

On

Selects Change UV Lamp feature . 

42

350 Days

25-1975

Change UV Lamp duration days .

43

OFF

Change Filter

On

Selects Change Filter feature .

44

200 Hrs

25-1975

Change Filter duration hours .

6

Содержание 1F95-1280

Страница 1: ... Thermostat Configuration Options Thermostat Applications Maximum Stages Heat Cool W Economizer Max Stage Heat Cool Single Stage 1 No Heat Pump SS1 Gas Oil Electric Heat Only Cool Only or Heat Cool Systems 2 or 3 wire Hydronic Zone Hot Water or Steam Systems 24 Volt or Millivolt 1 1 1 2 Multi Stage 2 No Heat Pump MS2 2 2 2 3 Heat Pump 1 Single Stage Compressor Heat Pump HP1 Single Stage Compressor...

Страница 2: ...he Power Stealing Switches Fig 1 should be left in the On position for most systems The information in the following table details the thermostat power method and switch options WARNING Thermostat installation and all components of the control system shall conform to Class II circuits per the NEC code INSTALLATION Figure 1 Thermostat Base Multi Stage 1F95 1280 2 AA Batteries Power Stealing Switche...

Страница 3: ...gured for Electric Heat Installer Configuration Menu selects O or B for changeover function Set to O terminal energized in Cool mode Set to B terminal energized in Heat emergency mode Power closed connection for SPDT 3 wire zone valve Fault or system malfunction indicator for Heat Pumps with L terminal connection COOLING CLASS II TRANSFORMER HOT 24VAC NEUTRAL 120VAC HEATING 120VAC Dual fuel option...

Страница 4: ...2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 2 9 3 0 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 3 19 2 1 11 10 15 16 9 8 17 13 12 4 18 14 A steady Cool Savings display indicates the feature is enabled in the installer menu A flashing Cool Savings display indicates the feature is active 15 Remote indicates that the indoor remote temperature sensor is being accessed Outdoor Remote indi cates the outdoor remote temperat...

Страница 5: ...s Continuous Display backlight 12 LO dL HI Selects Backlight Intensity 13 0 Temperature 5 LO to 5 HI Selects Adjustable Ambient Temperature Display range 5 LO to 5 HI 14 F C Selects F C Display temperature units in Fahrenheit or Celsius 15 On b OFF Selects audible Beeper On Off 16 On dS OFF Selects Daylight Saving Time calculation 17 On Heat AS OFF Selects Automatic Schedule for comfort temperatur...

Страница 6: ...ctory default setting is fast cycle FA Cr in all modes Heat Cool Emer To change to slow cycling SL Cr press touch keys or toggle between FA SL The cycle rates are below Mode Fast rate Slow rate Heat SS1 MS2 0 6 F 1 5 F Cool SS1 MS2 1 2 F 1 7 F Heat Pump HP1 HP2 1 2 F 1 7 F Emer Heat HP1 HP2 0 6 F 1 7 F 10 Select Compressor Lockout CL Selecting CL On will cause the thermostat to wait 5 minutes betw...

Страница 7: ...tting between 62 F and 98 F Temperature Limit icon will be displayed to the left of your setpoint temperature when using this feature Temperature Limit icon will flash if an attempt is made to adjust the temperature beyond the range selected 23 Cool Temperature Limit Range This feature adjusts the lowest setpoint temperature for cool The default setting is 45 F It can be changed to a setting betwe...

Страница 8: ...eat will not turn on The default setting is 60 but can be set in the range of 5 to 79 INSTALLER CONFIGURATION MENU If indoor temperature drops below 45 because of a pos sible heat pump malfunction the thermostat will turn off the pump and switch to Auxiliary heat Call for Service will display on screen There are two ways the thermostat will return to normal heat pump operation Press any key to ret...

Страница 9: ...below room tempera ture The heating system should stop operating Cooling 1 Press SYSTEM to select COOL 2 Press to adjust the thermostat setting below room tem perature The blower should come on immediately on high speed followed by cold air circulation The display should show System On If the setpoint temperature display is flashing the compressor lockout feature is operating see Configuration men...

Страница 10: ...inutes only in clock display 4 Press and hold either the or touch keys until you reach the correct minutes 5 Press Set Time once again to display year 6 Press either the or touch key until you reach the correct year 7 Press Set Time once again to display month 8 Press either the or touch key until you reach the correct month 9 Press Set Time once again to display date of the month along with day o...

Страница 11: ...gram all the heating temperatures during the day to a comfortable temperature and then lower the temperature 6 at night Auto Schedule Cool will program all of the cooling time periods to the same temperature Note Auto Schedule is available only when the thermostat is first powered on after the thermostat has been reset or anytime you turn AS on in the Configuration Menu item 18 AS Heat or 19 AS Co...

Страница 12: ...cil in your own program times and temperatures The 1F95 1280 comes configured for 7 day programming and can also be configured for 5 1 1 programming see configura tion section Factory settings are listed on Monday Saturday and Sunday If you are re programming a 5 1 1 day schedule pencil in your own times and temperatures directly below the factory times and temperatures If you are re programming a...

Страница 13: ...ration of the thermostat the current tempera ture displayed will be the weighted average of the local sensor and the remote sensor using the formula local sensor weight x local sensor temperature remote sensor weight x remote sensor temperature local sensor weight remote sensor weight Example Local sensor temperature is 80 and the remote sensor is 70 If weight is selected H4 the averaged temperatu...

Страница 14: ...stem operates correctly replace the thermostat Thermostat Setting Thermostat Thermometer Disagree 1 Thermostat thermometer setting requires adjustment The thermometer can be adjusted 4 degrees See Temperature Display Adjustment in the Configuration Menu section Furnace Air Conditioner Cycles Too Fast or Too Slow narrow or wide temperature swing 1 The location of the thermostat and or the size of t...

Страница 15: ...15 NOTES ...

Страница 16: ...White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co Homeowner Help Line 1 800 284 2925 www white rodgers com www emersonclimate com ...

Отзывы: