PROGRAMMING

Wired Remote Temperature Sensing

One remote temperature sensor can be installed indoor or 
outdoor and connected to the thermostat by a maximum 
cable length of 100 meters (300 feet) . Ter, S and - on 
the terminal block allow connection of the remote sensor . 
The thermostat must have 24 VAC Common connection to 
terminal C for the remote sensor to operate . The remote sen-
sor can be enabled or disabled in the Installer/Configuration 
menu, item 26 .
When remote sensor, 

Remote

, is selected 

Off 

(factory de-

fault), no remote sensor is enabled . When remote sensor is 
selected 

On

, the next step is to select the remote as indoor, 

Remote In

, or outdoor, 

Remote Outdoor

 . If the remote is se-

lected as Remote In, an additional step will be to select if the 
temperature shown on the display will be from the thermostat, 

LS On

, or the remote sensor 

LS Off

 .

In normal operation, when a remote sensor is enabled the 
time digits of the display will alternate between the time and 
the remote temperature for three seconds each . Above the 
remote temperature will be Remote, for indoor sensor or 

Outdoor Remote

, for outdoor sensor . If the remote sensor is 

an indoor sensor and the local display has been disabled, the 
temperature displayed as the room temperature will be the 
remote sensor temperature .
Sensing Range: 
Outdoor temperature range is -40

o

F to 140

o

Indoor temperature range is 32

o

F to 99

 o

F

Averaging or Weighting Remote Sensors

The thermostat will weight or average the temperature of the 
indoor remote sensor with the local sensor in the thermostat 
for each program period . The averaging will be active only 
when the local sensor and the indoor remote sensor are both 
functional and enabled in the Installer/Configuration menu .
When the thermostat is in the Set Schedule mode, the weight 
of the indoor sensor will be shown in the current temperature 
digits of the display . The weight will show as 

A2

 (average and 

default), 

H4

 (high) or 

L1

 (low) . Pressing the   and   keys at 

the same time will change the weight for the program period . 
The weight of the thermostat sensor is fixed . 
In normal operation of the thermostat, the current tempera-
ture displayed will be the weighted average of the local 
sensor and the remote sensor using the formula (local sensor 
weight x local sensor temperature) + (remote sensor weight x 
remote sensor temperature) / (local sensor remote 
sensor weight) .

Example: Local sensor temperature is 80° and the remote 
sensor is 70° . 
If weight is selected 

H4

, the averaged temperature of 72° will 

be displayed .
(1 x 80) + (4 x 70) / 5 = 72° 
If weight is selected 

A2

, the average temperature of 73° will 

be displayed .
(1 x 80) + (2 x 70) / 3 = 73 .3°
If weight is selected

 L1

, the average temperature of 75° will 

be displayed .
(1 x 80) + (1 x 70) / 2 = 75°
The example shows that the weight selected would prioritize 
the overall averaged temperature between the two sensors . 
The high weight selection caused the remote sensor to have 
a higher influence in the calculated temperature average than 
the local sensor and the low weight selection caused the 
remote sensor to have less influence . 

Dual Fuel Temperature Setpoint

When the thermostat is configured for Heat Pump mode and 
the Dual Fuel feature is selected on, the thermostat can moni-
tor the outside temperature using remote sensor F145-1378 
or use software logic to determine when to switch to gas heat 
and shut down the compressor . This eliminates the need for a 
fossil fuel kit . 
The user selectable temperature is called the dual fuel tem-
perature setpoint, 

dF

 and is set in the Installer/Configuration 

menu, items 32 or 33 . With outdoor remote sensor installed 
and enabled, the dual fuel temperature setpoint (menu item 33) 
can be set to a temperature of 5° through 50° . When outdoor 
remote sensor is not installed, a software logic based dual fuel 
number (menu item 32) from 01 to 09 can be selected . 
After the dual fuel temperature setpoint is set and 

 is 

pressed, a delay, 

Cd

, can be set for compressor shutdown 

after the auxiliary stage is energized . This delay can be set 
from 0 seconds to 99 seconds to minimize the time that the 
system may blow cooler air until the alternate source of heat 
comes on . Default setting for delay is 60 . When setting the 
delay, if the   or   keys are held depressed, the setpoint 
will increase or decrease at the rate of one degree every half 
second for the first three seconds and double the speed after 
three seconds .

13

Содержание 1F95-1280

Страница 1: ... Thermostat Configuration Options Thermostat Applications Maximum Stages Heat Cool W Economizer Max Stage Heat Cool Single Stage 1 No Heat Pump SS1 Gas Oil Electric Heat Only Cool Only or Heat Cool Systems 2 or 3 wire Hydronic Zone Hot Water or Steam Systems 24 Volt or Millivolt 1 1 1 2 Multi Stage 2 No Heat Pump MS2 2 2 2 3 Heat Pump 1 Single Stage Compressor Heat Pump HP1 Single Stage Compressor...

Страница 2: ...he Power Stealing Switches Fig 1 should be left in the On position for most systems The information in the following table details the thermostat power method and switch options WARNING Thermostat installation and all components of the control system shall conform to Class II circuits per the NEC code INSTALLATION Figure 1 Thermostat Base Multi Stage 1F95 1280 2 AA Batteries Power Stealing Switche...

Страница 3: ...gured for Electric Heat Installer Configuration Menu selects O or B for changeover function Set to O terminal energized in Cool mode Set to B terminal energized in Heat emergency mode Power closed connection for SPDT 3 wire zone valve Fault or system malfunction indicator for Heat Pumps with L terminal connection COOLING CLASS II TRANSFORMER HOT 24VAC NEUTRAL 120VAC HEATING 120VAC Dual fuel option...

Страница 4: ...2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 2 9 3 0 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 3 19 2 1 11 10 15 16 9 8 17 13 12 4 18 14 A steady Cool Savings display indicates the feature is enabled in the installer menu A flashing Cool Savings display indicates the feature is active 15 Remote indicates that the indoor remote temperature sensor is being accessed Outdoor Remote indi cates the outdoor remote temperat...

Страница 5: ...s Continuous Display backlight 12 LO dL HI Selects Backlight Intensity 13 0 Temperature 5 LO to 5 HI Selects Adjustable Ambient Temperature Display range 5 LO to 5 HI 14 F C Selects F C Display temperature units in Fahrenheit or Celsius 15 On b OFF Selects audible Beeper On Off 16 On dS OFF Selects Daylight Saving Time calculation 17 On Heat AS OFF Selects Automatic Schedule for comfort temperatur...

Страница 6: ...ctory default setting is fast cycle FA Cr in all modes Heat Cool Emer To change to slow cycling SL Cr press touch keys or toggle between FA SL The cycle rates are below Mode Fast rate Slow rate Heat SS1 MS2 0 6 F 1 5 F Cool SS1 MS2 1 2 F 1 7 F Heat Pump HP1 HP2 1 2 F 1 7 F Emer Heat HP1 HP2 0 6 F 1 7 F 10 Select Compressor Lockout CL Selecting CL On will cause the thermostat to wait 5 minutes betw...

Страница 7: ...tting between 62 F and 98 F Temperature Limit icon will be displayed to the left of your setpoint temperature when using this feature Temperature Limit icon will flash if an attempt is made to adjust the temperature beyond the range selected 23 Cool Temperature Limit Range This feature adjusts the lowest setpoint temperature for cool The default setting is 45 F It can be changed to a setting betwe...

Страница 8: ...eat will not turn on The default setting is 60 but can be set in the range of 5 to 79 INSTALLER CONFIGURATION MENU If indoor temperature drops below 45 because of a pos sible heat pump malfunction the thermostat will turn off the pump and switch to Auxiliary heat Call for Service will display on screen There are two ways the thermostat will return to normal heat pump operation Press any key to ret...

Страница 9: ...below room tempera ture The heating system should stop operating Cooling 1 Press SYSTEM to select COOL 2 Press to adjust the thermostat setting below room tem perature The blower should come on immediately on high speed followed by cold air circulation The display should show System On If the setpoint temperature display is flashing the compressor lockout feature is operating see Configuration men...

Страница 10: ...inutes only in clock display 4 Press and hold either the or touch keys until you reach the correct minutes 5 Press Set Time once again to display year 6 Press either the or touch key until you reach the correct year 7 Press Set Time once again to display month 8 Press either the or touch key until you reach the correct month 9 Press Set Time once again to display date of the month along with day o...

Страница 11: ...gram all the heating temperatures during the day to a comfortable temperature and then lower the temperature 6 at night Auto Schedule Cool will program all of the cooling time periods to the same temperature Note Auto Schedule is available only when the thermostat is first powered on after the thermostat has been reset or anytime you turn AS on in the Configuration Menu item 18 AS Heat or 19 AS Co...

Страница 12: ...cil in your own program times and temperatures The 1F95 1280 comes configured for 7 day programming and can also be configured for 5 1 1 programming see configura tion section Factory settings are listed on Monday Saturday and Sunday If you are re programming a 5 1 1 day schedule pencil in your own times and temperatures directly below the factory times and temperatures If you are re programming a...

Страница 13: ...ration of the thermostat the current tempera ture displayed will be the weighted average of the local sensor and the remote sensor using the formula local sensor weight x local sensor temperature remote sensor weight x remote sensor temperature local sensor weight remote sensor weight Example Local sensor temperature is 80 and the remote sensor is 70 If weight is selected H4 the averaged temperatu...

Страница 14: ...stem operates correctly replace the thermostat Thermostat Setting Thermostat Thermometer Disagree 1 Thermostat thermometer setting requires adjustment The thermometer can be adjusted 4 degrees See Temperature Display Adjustment in the Configuration Menu section Furnace Air Conditioner Cycles Too Fast or Too Slow narrow or wide temperature swing 1 The location of the thermostat and or the size of t...

Страница 15: ...15 NOTES ...

Страница 16: ...White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co Homeowner Help Line 1 800 284 2925 www white rodgers com www emersonclimate com ...

Отзывы: