ESR-Series. User manual
70
Figure 51 – Device rack installation
3.3 ESR-1000, ESR-1200, ESR-1500, ESR-1511, ESR-3100, ESR-1700 power module installation
ESR-1000/1200/1500/1511/3100/1700 router can operate with one or two power modules. The second power
module installation is necessary when the device operates under strict reliability requirements.
From the electric point of view, both places for power module installation are identical. In the context of device
operation, the power module can be in the main and reserve slot. For information on priority see tables
«Description of connectors, LEDs and controls located on router». Power modules can be inserted and
removed without powering the device off. When additional power module is inserted or removed, the router
continues operation without reboot.
Figure 52 – Power module installation
Device ventilation system is implemented using 'front-rear' layout. Vents are located on the front and
side panels of the device; ventilation modules are located at the rear. Do not block air inlet and outlet
vents to avoid components overheating and subsequent device malfunction.