34
User Guide •
Smartpack S Controller
About Power System Configuration
350030.013, 1v0-2012-06
The example below shows typical Alarm Output Group assignment in a
Smart-
pack S
-based system.
Alarm Configuration > Outputs
#
Description, Alarm Groups
Output
1
2
3
4
5
6
LVBD
LVLD1
Note
1
Major Alarm, AOG
2
Minor Alarm, AOG
3
Mains Alarm, AOG
4
Fuse Alarm, AOG
5
High Battery Alarm, AOG
6
Low Battery Alarm, AOG
7
Rectifier Alarm, AOG
8
Gen-Set AOG
9
Alarm Group 9
10
Alarm Group 10
---
---
17
Alarm Group 17
18
OutpBlocked, AOG
19
LVBD, AOG
20
LVLD, AOG 1
-----
-----
-----
In the example above,
• Alarm relay output 1 is used for external common alarm signaling
• Alarm Output Group 18, “OutpBlocked, AOG”
If an external warning is necessary, you can assign output relays to the
“OutpBlocked, AOG” group, e.g. to activate a lamp or alarm bell when
the alarm output relays are blocked.
Read more in topic
"Alarm Outputs Isolation (Output Blocked)" on page
• Alarm Groups 9 through 17 are unused, and can be assigned when re-
quired