About Power System Configuration
User Guide •
Smartpack S Controller
23
350030.013, 1v0-2012-06
Example of Battery Test Log table displayed in
Smartpack S
Controller’s submenu:
Logs/Report > Battery Test Log
#
StartTime
Durat.
Typ
Descr
Amp
Q%
EndV
Note
09:58
34
Manual
-----------------
-68
70%
45.49
----------------
Using
WebPower
or
PowerSuite
you can also display the test results for a battery
test in a line graph.
Inventory Report
The Inventory Report presents information that describes the power system, the
site’s name , serial number, installation and service dates, software name, etc.
Example of Inventory Report table in
Smartpack S
Controller’s submenu:
Logs/Report > Inventory Report
#
Description
Note
Company
Site
Model
Install Date
Serial N
Service Date
Responsible
Message 1
Message 2
(Installed HW and SW info, part #, serial #, version #, etc.)
6 - Statistics options
This logical group collects and presents relevant system data and calculated sta-
tistics, such as average results, peak values, etc.
Example of the Statistics table available in
Smartpack S
Controller’s submenu:
Statistics
#
Description
Reset
Average
Peak
Note
BatteryVoltage
No
52,48
52,61
BatteryCurrent
No
-35
0
Battery Temp
No
41
0
Load Current
No
35
50
Rectifier Current
No
75
120
Mains Volt 1
No
225
235
7 - Commissioning options
This logical group presents a generic description of the steps required to carry out
commissioning tasks of the power system.
Refer also to the system’s user documentation, and to the Commissioning Proce-
dure pull-out list in the system’s quick start guide.