User Guide •
Smartpack S Controller
About Power System Configuration
350030.013, 1v0-2012-06
The examples below show typical configuration parameters for these alarm moni-
tors.
Parameters with “(x)” references in the Note column are described in more detail at
the end of this chapter.
Parameters for Logical Alarm Monitors (L1)
Example to monitor logical states such as Open/Close or Yes/No.
#
Description
Value
Unit/Label
Note
Monitor – Enable/Disable?
Enable
Activates or deactivates the alarm monitor
Manual Reset
Disabled
Or “All Levels” or “MajorHigh Only” (a)
Hysteresis
000
(not applicable)
TimeDelay
7
Seconds
Selects among delay time options (b)
MinorHigh AlarmGroup
Major Alarm
Selects the alarm group to activate
Parameters for Numerical Alarm Monitors (N1)
Example to monitor numeric values such as the number of rectifiers, errors, etc.
#
Description
Value
Unit/Label
Note
Monitor – Enable/Disable?
Enable
Activates or deactivates the alarm monitor
Manual Reset
Disabled
Or “All Levels” or “MajorHigh Only” (a)
Hysteresis
0000
Units
(not applicable)
TimeDelay
2
Seconds
Selects among delay time options (b)
MajorHigh AlarmLevel
001
Units
Upper limit
MajorHigh AlarmGroup
Major Alarm
Selects the alarm group to activate
MinorHigh AlarmLevel
001
Units
Lower limit
MinorHigh AlarmGroup
Minor Alarm
Selects the alarm group to activate
Parameters for Numerical Alarm Monitors (N2%)
Another example to monitor numeric values such as the percent of battery capac-
ity, etc.
#
Description
Value
Unit/Label
Note
Monitor – Enable/Disable?
Enable
Activates or deactivates the alarm monitor
Manual Reset
Disabled
Or “All Levels” or “MajorHigh Only” (a)
Hysteresis
2
%
(b)
TimeDelay
10
Seconds
Selects among delay time options (b)
MajorHigh AlarmLevel
95
%
Upper limit
MajorHigh AlarmGroup
Major Alarm
Selects the alarm group to activate
MinorHigh AlarmLevel
80
%
Lower limit
MinorHigh AlarmGroup
Minor Alarm
Selects the alarm group to activate