4. Insert the O-ring with the mounting pin in the sensor hole of the ball valve using turning movements
(Fig. AA, item 3).
5. Position the O-ring in its final position using the other end of the mounting pin
(Fig. AA, item 4).
6.
Push the fixing screw onto the temperature sensor.
7. Place the mounting pin with the sleeve end over the temperature sensor as far as it will go.
8. The temperature sensor is held in the fixing screw.
9. Press in the slotted pin on the temperature sensor coupling using a pair of pliers (Fig. AA, item 6).
10. Remove the mounting pin from the temperature sensor (Fig. AA, item 5).
11. Now insert the temperature sensor with the adapter coupling into the ball valve and tighten the
brass or plastic screw by hand (2-3 Nm) (Fig. AA, item 7).
Installation in a pocket
The pockets are best installed in T-pieces with a 45 ° or 90 ° angle. The tip of the pocket must point in
the opposite direction to the direction of flow and must be located in the middle of the pipe (Fig. BB,
item 1-5). The temperature sensors must be sealed after installation in the pockets.
Fig. BB Example for mounting and sealing