22
Analogue output module
2 passive outputs
External power supply: 10 … 30 V DC
Current loop 4 … 20 mA
where 4 mA = 0 value; 20 mA = programmed max. value
Overload up to 20.5 mA, then fault current
Errors are generated at 3.5 mA or 22.6 mA (programmable)
Output values: power, flow rate, forward temperature, return temperature, difference
temperature
Maximal cable length 10 m (acc. to EN 1434)
To use the analogue output module an external power supply is necessary.
The outputs are marked “1” and “2” on the terminal with the respective polarity “+” and “-”.
Fig. P
Analogue module
Connection diagram:
+ 1 -
Analogue output 1
10 … 30V DC