21
Module IN-OUT (Pulse-in and -output)
The module IN-OUT is equipped with 2 pulse inputs and 1 pulse output.
The pulse inputs have the following specification:
The two pulse inputs can be programmed independently of each other with values of 1, 2.5, 10,
25, 100, 250, 1000 or 2500 litres per pulse.
Possible units are all the energy units available in the meter, such as kWh/pulse and GJ/pulse,
but also volume units like l/pulse, m³/pulse, or no units.
The input frequency is in the range 0 – 8 Hz, min. pulse duration 10 ms
Input resistance 2.2 M
Ω
Terminal voltage 3 V DC
Cable length < 10 m
The pulse output has the following specification:
External power supply Vcc = 3 – 30 V DC
Output
current
≤
20 mA with a residual voltage of
≤
0.5 V
Open collector (drain)
Output
frequency
≤
4 Hz
Pulse duration: 125 ms ±10 %
Pulse
break:
≥
125 ms -10 %
Volume pulse value is programmable as desired (default: last digit in display)
No floating contact (not galvanic isolated)
Pulse input 1 is marked “I1 -
┴
” on the module and “IN1” in the display, pulse input 2 “I2 -
┴
” on the
module and “IN2” in the display (Fig. O, item 1).
The pulse output is marked “01 -
┴
” on the terminal and “Out1” in the display (Fig. O, item 2).
Fig. O
Module IN-OUT
1
Terminals for pulse inputs
2
Terminals for pulse output
1
2