Note: Manual defrosts also end after the defrost duration (
dd
) or on reaching the defrost termination
temperature (
dtd
).
For more information about the parameters used in
defrost
:
l
See "Defrost duration (dd)" on page 73
l
See "Defrost interval (dE)" on page 73
l
See "Defrost termination temperature (dtd)" on page 71
5.2
Evaporator fan management
EMS controllers, depending on model, can be configured to manage the evaporator fan.
EMS controllers always run the evaporator fan when the compressor is running.
For periods that the compressor is not running, the EMS controllers run the evaporator fan according
to the evaporator fan cycle.
Note:
l
The evaporator fan cycle is not applied whilst the compressor is not running during a defrost period.
The evaporator fan cycle is defined by the fan cycle on (
FC O
) and fan cycle off (
FC F
) parameters.
The fan cycle starts with a fan cycle on (
FC O
) period as shown below.
EMS controllers stop the evaporator when the cooler door is opened.
To prevent excessive condensation on the evaporator in environments where warm, and presumed
humid air is present, the controller runs the evaporator fan continuously if the temperature exceeds
33 of 86
27 February 2014