9.17
Delay to saving (dS)
The table below details the delay to saving (
dS
) parameter.
Display
Description
Defines the delay in switching to the
saving mode
from
ready mode
.
The delay starts at the end of the last active 30 minute
period of the
ready mode
.
Considerations
Must be set in multiples of 30 minutes.
Range
0 to 120 minutes (in multiples of 30 minutes)
Global default
00 (no delay)
9.18
Lights delay (Ld)
The table below details the light delay (
L d
) parameter.
Display
Description
Defines the delay to switch off the cooler lights after the EMS controller
switches to the
saving mode
.
Considerations
l
Must be set in multiples of 30.
l
Should only take affect once Delay to saving (
dS
) has completed.
Range
0 to 120 minutes
Global default
00 (no delay)
9.19
Saving restart period (Sr)
The table below details the saving restart period (
S r
) parameter.
Display
Description
Cooler runs at the
ready mode
temperature for the duration of this period to
ensure that the cooler is at the set point prior to retail outlet opening time.
Considerations
l
Set and verified by OEMs through the test protocol to ensure that product tem-
peratures are within specification when outlets open.
l
Must be set in multiples of 30 minutes.
l
Depending on Ar setting, the cooler lights would normally be on.
Range
0 to 240 minutes (in multiples of 30 minutes)
Global default
120 minutes
9.20
Refrigeration system failure (Ct)
The table below details the refrigeration system failure (
C t
) parameter.