Elstat ems75 Sub-Zero Скачать руководство пользователя страница 36

l

Passing peak current through the windings of the compressor motor

l

Switching off the refrigeration system on the thermal overload protection

l

Short-cycling the refrigeration system.

However, if

ready mode

and

saving mode

differential temperatures are too small or if the compressor

rest time (

rt

) is too short, the EMS controller cycles the compressor on the compressor rest time

(

rt

) as the compressor rest time (

rt

) overrides the differential temperatures.

If the compressor runs continuously for too long without reaching the set point (

S P

) temperature, a

refrigeration system failure (

rS F

) alarm activates alerting to possible problems with the refrigeration

system.

EMS controllers can monitor the refrigeration system temperature using a condenser sensor. Mon-
itoring the refrigeration system temperature can help detect problems, such as a blocked con-
denser.

If the temperature measured on the condenser sensor reaches the condenser high temperature
(

C t

), the EMS controller disables the compressor and activates the (

Ht

) alarm. The condenser high

temperature (

C t

) is set by measuring the refrigeration system temperature when the condenser is

75% blocked.

EMS controllers manage the failure of a temperature sensor as follows:

l

Appliance sensor failures indicated by

PF1

alarms, EMS controllers stop running the compressor and then

waits 60 seconds before rebooting (switch off and then switch on).
If the fault continues, the EMS controller repeats and continues the cycle.

l

Condenser sensor failures indicated by

PF2

alarms, EMS controllers continue running the compressor. EMS

controllers alternate the display between

PF2

and the appliance sensor temperature.

l

For evaporator failures indicated by

PF3

alarms, EMS controllers continue running the compressor. EMS con-

trollers alternate the display between

PF3

and the appliance sensor temperature.

Note:

l

Ht alarms do not apply to CO2 coolers

For more information about the parameters used in

compressor management

:

l

See "Refrigeration system failure (Ct)" on page 72

l

See "Differential (dIF)" on page 67

l

See "Compressor rest time (rt)" on page 71

l

See "Set point (SPC or SPF)" on page 67

l

See "Saving set point (SSP)" on page 68

For trouble shooting information:

l

See "How to troubleshoot refrigeration system failure (rSF) alarms" on page 62

l

See "How to troubleshoot temperature sensor alarms" on page 63

5.6

Product temperature

EMS controllers manage the product temperature. EMS controllers use an appliance sensor to meas-
ure the air temperature of the refrigeration compartment.

The location of the appliance sensor within the refrigeration compartment depends on the cooler
type.

35 of 86

27 February 2014

Содержание ems75 Sub-Zero

Страница 1: ...ems75sz Sub Zero Firmware U09 n05 27 February 2014 www elstatgroup com ...

Страница 2: ...3 10 Control display module 13 3 11 How to mount the control display module 15 3 12 External control display module electrical connections 16 3 13 Internal control display module electrical connections 17 3 14 Environmental ratings 17 4 User guide 18 4 1 Power up sequence 18 4 2 Function buttons ems sub zero 18 4 3 Indicators 19 4 4 Display codes 19 4 5 What are the menus 20 4 6 How to access the ...

Страница 3: ...sensor 51 7 5 How to mount the evaporator sensor 51 7 6 Door switch 52 7 7 How to mount the door switch 52 7 8 How to mount door switches on double door coolers 53 7 9 Motion sensor ems75sz 54 7 10 Motion sensor 55 7 11 How to mount a remote motion sensor 55 8 How to troubleshoot ems75sz 57 8 1 Troubleshooting 57 8 2 How to check that EMS controllers are working correctly 57 8 3 How to troubleshoo...

Страница 4: ...val dE 73 9 22 Defrost duration dd 73 9 23 Defrost method dF 73 9 24 Defrost termination method dtF 74 9 25 Fan cycle on FCO 74 9 26 Fan cycle off FCF 74 9 27 Display stability d2 75 9 28 Buzzer enable b0 75 9 29 Buzzer duration b1 76 9 30 Alarm delay Ad 76 9 31 Activity frequency AF 76 9 32 Motion sensor enable Sn 77 9 33 Saving temperature disable PEr 77 9 34 Learning period LP 77 9 35 Display d...

Страница 5: ...h as l Single door coolers l Double door coolers l Open front coolers l Vending machines l Sub zero beer coolers 1 1 About this reference guide The purpose of this guide is to explain in detail all information regarding Elstat controllers including the user interface parameters accessories and troubleshooting Complimentary information is also available from Elstat such as accessory lists accessory...

Страница 6: ...Elstat products have been designed to minimise any risks associated with water ingress and all con trollers are IPX5 certified The OEM or installer is responsible to ensure that local country laws and regulatory requirements are met 5 of 86 27 February 2014 ...

Страница 7: ...s Serving temperature Appliance sensor measures the air temperature of the refrigeration compartment Self learning determines when the product should be at the ready mode temperature the optionalserving temperature or the saving mode temperature Refrigeration alarms Refrigeration systemalarms can alert to possible cooling problems and an optionalcondenser sensor can alert to problems such as block...

Страница 8: ...e control unit and the relays to switch the following cooler components Feature Description Compressor relay Switches the compressor to manage the temperature of the refrigeration com partment Evaporator fan relay Switches the evaporator fan to minimize heat transfer to products when the com pressor is not running Auxiliary relay Switches a defrost heater to a solenoid valve for hot gas defrosts L...

Страница 9: ...s 3 3 2 LED indicators Indicator Function Colour Compressor On when the compressor is running Green Evaporator fan On when evaporator fan is running Red Saving temperature disable On if the saving mode temperature is disabled The controller maintains ready mode temperature at alltimes Red Motion On when motion is detected Red 3 4 ems75sz relay ratings The table below details the relay ratings of t...

Страница 10: ...5 Temperature input ranges The table below shows the temperature input ranges of the EMS sub zero controllers for each sensor type Sensor Input range ºC Input range ºF Appliance sensor 10ºC to 23 3ºC 0 5ºC 14ºF to 74ºF 1ºF Condenser sensor 50ºC to 125ºC 5 0ºC 122ºF to 257ºF 10ºF Evaporator sensor 30ºC to 15ºC 0 5ºC 22ºF to 59ºF 1ºF Note l The NTC thermistor fromElstat is rated at 35ºC to 125ºC 31º...

Страница 11: ...o interface cable of the controldisplay module The power supply module must be mounted vertically with the cables exiting vertically downwards The power supply module has an Ingress Protection IP rating of IPX5 which means the power supply module is protected against water jets Caution l The power supply module must be located in a non refrigerated area of the cooler The power supply module must n...

Страница 12: ...following characteristics l Head maximumdiameter 7 8mm 0 31in and minimumdiameter 6 2mm 0 24in l Thread maximumdiameter 4 8mm 0 19in The screws must be tightened to a maximum torque of 0 5Nm 0 37lb f ft Caution l Using rivets to mount the power supply module invalidates the warranty Cable routing to the EMS controller is critical as water can trace or follow the cable downwards Therefore immediate...

Страница 13: ...brating components Secure cable routing looms with clips where ever possible 3 9 1 Power supply module dimensions The dimensions of the fixing holes are shown below The following is an example of the Power Supply Module mounted but not connected 12 of 86 27 February 2014 ...

Страница 14: ... to be mounted on the cooler with the display visible to outlet customers and includes an integrated motion sensor For example mount in the header panel of the cooler l The internalvariant is designed to be mounted within the cooler cabinet and does not have an integrated motion sensor For example mount into an internalheader panel The ems75sz controller display module is available in two styles a...

Страница 15: ...troller display modules CDMs are made fromfood grade materials and safe for internal installation l The controldisplay module has an IP rating of IPX5 protection against water jets Caution 14 of 86 27 February 2014 ...

Страница 16: ... and is secured using the fitted clips The aperture dimensions are shown below To mount the control display module remove the retaining clip and insert the control display module into the aperture as shown below Then place the retaining clip into position as shown below Finally secure the retaining clip as shown below and ensure that the control display module is held firmly in position 15 of 86 2...

Страница 17: ...ntrol display module electrical connections The electrical connections of the external variant control display module as follows Label Description Connectors 1 Interface cable to power supply module 2 Parameter programming port 3 aux Evaporator sensor 4 door Door switch 5 ht Condenser sensor 6 app Appliance sensor 16 of 86 27 February 2014 ...

Страница 18: ... has a micro connector 3 14 Environmental ratings The table below details the general characteristics of the ems75sz Characteristic Power supply module Control display module IP rating IPX5 IPX4 Maximum operating tem perature 55ºC 131ºF 55ºC 131ºF Minimumoperating temperature 0ºC 32ºF 0ºC 32ºF Housing material Black polycarbonate Black polycarbonate Before beginning installation remove all protect...

Страница 19: ...ws the appropriate display code For example the temperature or the word USE 4 2 Function buttons ems sub zero The EMS controller buttons access the EMS controller menus to view parameter values reset the EMS controller and to run test routines The EMS controller buttons perform the following functions Button Name Function end user Function service engineer Defrost Starts a defrost cycle Use as par...

Страница 20: ...that EMS controllers are working correctly on page 57 Saving mode EMS controllers keep products at the saving mode temperature unless the saving temperature is disabled The saving temperature LED shows whether the saving mode tem perature is disabled The cooler lights are off unless the light delay Ld parameter keeps the lights on for a short period after the EMS controller switches to the savingm...

Страница 21: ...ion systemfailure rSF alarms on page 62 Alarm Appliance sensor failure See How to troubleshoot temperature sensor alarms on page 63 Alarm Condenser sensor failure Alarm Evaporator sensor failure 4 5 What are the menus The table below describes the EMS controller menus Use the Down button to scroll through the menu and the Set button to select Menu Display Description Parameter list Displays the pa...

Страница 22: ...a unique sequence of button operations The password is supplied to OEMs installers and service engineers separately Step Action Display 1 Press and hold the Set button 2 The EMS display shows 3 Press the Set button four times x 4 4 Press the Up button once x 1 5 Press the Down button twice x 2 6 Press the Defrost button twice x 2 7 The EMS display shows You have successfully entered the EMS menu 4...

Страница 23: ...ge 67 4 See Calibration 1 CA1 on page 68 5 See Calibration 2 CA2 on page 68 6 See Saving set point SSP on page 68 7 See Saving differential Sd on page 69 8 See Freeze up protection dtt on page 69 9 See Fan set point FSP on page 69 10 See Condenser high temperature Ht on page 70 11 See Defrost activation temperature ddt on page 70 12 See Defrost termination temperature dtd on page 71 13 See Compres...

Страница 24: ...See Saving temperature disable PEr on page 77 31 See Learning period LP on page 77 32 See Display dIS on page 78 33 See Marketing mode Ar on page 78 34 See Defrost heater dHr on page 78 Sub zero exclusive parameter 4 8 How to run the test routine tst The test routine tests the following l Allload relays l Analogue inputs temperature sensors and door switch l Motion sensor Should a problem be suspe...

Страница 25: ...t menu 6 The EMS display shows 7 Press the Set button to test the seven segment display 8 The EMS display shows 9 Press the Set button to start the relay test 10 The EMS display shows 11 Press the Down button to start the relay test 4 8 1 The relay test Button Display Test Check Compressor relay Compressor is running and compressor LED is on Light relay Cooler lights are on 24 of 86 27 February 20...

Страница 26: ...frost button together 13 The EMS display shows 14 Press the Down button to begin the Heater relay test 4 8 2 The heater relay test Button Display Test Check Heater relay Heating element or solenoid valve switches on Relay off Relays are off Note To switch off the relays that are on press the defrost button Step Action Display 15 Press the Set button and the Defrost button together 25 of 86 27 Febr...

Страница 27: ...ce sensor temperature Displayed temperature is correct Door switch Door is open dO or closed CLO Condenser sensor temperature Displayed temperature is correct Between 51 0 and 125 C Evaporator sensor temperature 4 8 4 The motion sensor test Step Action Display 18 Press the Setbutton and the Defrost button together 19 The EMS display shows 26 of 86 27 February 2014 ...

Страница 28: ...nu button and the Defrost button together The test routine ends 4 9 How to view the last three alarms FLt It is possible to view the last alarms and understand problems that have occurred with the EMS con troller Step Action Display 1 Press and hold the Setbutton 2 The EMS display shows 3 Enter the appropriate password to access the menu 4 The EMS display shows 5 Press the Down button and scrollto...

Страница 29: ...s occurred Adoor open alarmhas occurred Please note l The alarms may have been cleared or cancelled by the retailoutlet operators 4 10 Passwords The password to enter the EMS controller menu and perform a half reset is as follows Step Action Display 1 Press and hold the Set button 2 The EMS display shows 3 Press the Set button four times x 4 4 Press the Up button once x 1 28 of 86 27 February 2014...

Страница 30: ...r the self learning matrix if the EMS controller has been unable to detect activity correctly for example the view of the motion sensor was blocked or if the cooler has been moved to a new location Step Action Display 1 Press and hold the Set button 2 The EMS displays shows 3 Enter the button sequence of the menu entry password 4 Press the Set button four times x 4 5 Press the Up button once x 1 2...

Страница 31: ...ics when first powered up Statistics provide information on the following dependent on firmware l Activity Average number of motion counts and door openings l Compressor Average number of compressor cycles and totalcompressor runtime l Operation Settings of the activity frequency AF parameter and the saving temperature disable PEr parameter l Temperature Lowest highest and average temperature meas...

Страница 32: ...past 7 days 7 x 24 hour periods Note that the average is a moving average Compressor runtime Total number of hours that the compressor has run since the EMS controller was first powered up or since the last full reset Door openings Average number of door openings per day 24 hour period during the past 7 days 7 x 24 hour periods Note that the average is moving average Highest temperature Highest te...

Страница 33: ...orator fan to manage the temperature of the refrigeration compartment This is optionalfor EMS controllers and dependent on controller specification l Lights EMS controllers manage the cooler lights for marketing and energy saving purposes Note l Dependent on controller and sensor configuration 5 1 Defrost Glass Door Cooler GDC firmware Defrost cycles minimizes the risk of the evaporator icing up T...

Страница 34: ...ning For periods that the compressor is not running the EMS controllers run the evaporator fan according to the evaporator fan cycle Note l The evaporator fan cycle is not applied whilst the compressor is not running during a defrost period The evaporator fan cycle is defined by the fan cycle on FCO and fan cycle off FCF parameters The fan cycle starts with a fan cycle on FCO period as shown below...

Страница 35: ...e and optionally sounds an alarm buzzer Buzzer enable b0 defines whether to sound a warning buzzer for alarm conditions Buzzer duration b1 defines the duration of the buzzer for alarm conditions Note l For door open alarms the buzzer sounds regardless of the buzzer enable b0 setting For more information about the parameters used in alarms l See Buzzer enable b0 on page 75 l See Buzzer duration b1 ...

Страница 36: ...s l Appliance sensor failures indicated by PF1 alarms EMS controllers stop running the compressor and then waits 60 seconds before rebooting switch off and then switch on If the fault continues the EMS controller repeats and continues the cycle l Condenser sensor failures indicated by PF2 alarms EMS controllers continue running the compressor EMS controllers alternate the display between PF2 and t...

Страница 37: ...calibration 1 CA1 can add an offset to the temperature measured on the appliance sensor l See Calibration 1 CA1 on page 68 EMS controllers can be set to use Celsius C or Fahrenheit F set by the Celsius or Fahrenheit CF parameter l See Celsius or Fahrenheit CF on page 67 36 of 86 27 February 2014 ...

Страница 38: ...arning period that is aimed for outlets with regular daily patterns such as 7 11 shops For a 1 day learn ing period the EMS controller runs in the ready mode for the first day 24 hours l 7 day learning period that is aimed for outlets with varied opening hours such as working days weekends closed on Sundays and so on For a 7 day learning period the EMS controller runs in the ready mode for the fir...

Страница 39: ...ver if power is lost for more than 3 days controllers clear the self learning matrix when power is restored and starts from the learning period again 6 1 How EMS controllers work example After the learning the activity patterns during the learning period EMS controllers work as follows 1 Prior to the outlet opening the EMS controller ensures that the products are at the correct serving tem peratur...

Страница 40: ...ete 7 day self learning matrix as follows l 1 day learning period the EMS controller runs in ready mode for the first day 24 hours The EMS controller then uses the self learning matrix of day 1 for the next six days to build a complete 7 day self learning matrix l 7 day learning period the EMS controller runs in the ready mode for the first 7 days to build a complete 7 day self learning matrix To ...

Страница 41: ...l Day 6 the EMS controller runs in the ready mode from08 00 to 14 00 l Day 7 the EMS controller remains in the savingmode Note l The self learning matrix starts the moment the EMS controller is first switched on and is not synchronized with calendar days However the diagrambelow starts at 00 00 on Day 1 for clarity 6 4 Activity EMS controllers learn when retail outlets are open or closed by monito...

Страница 42: ...equency AF can automatically determine the most appropriate activity frequency EMS controllers using The EMS controller then starts the learning period after the 48 hours required to determine the activity frequency The EMS controller must be powered up for the complete 48 hour period If power is lost during the 48 hour period the EMS controller restarts determining the activity fre quency again 6...

Страница 43: ...the state frommonitor 1 to saving 0 Note l The amount of activity required to change the state frommonitor 1 to ready 2 depends on the setting of the activity frequency AF parameter Therefore at the end of day 1 first 24 hours the EMS controller has set all the 30 minutes to ready 2 or saving 0 depending the outlet activity pattern as shown in the example matrix EMS controllers then copy the patte...

Страница 44: ... were set to saving 0 to mon itor 1 as shown in the following example matrix At the end of week 1 the EMS controller has updated the self learning matrix for the outlet activity pattern Note that differences for activity patterns learnt on day 2 take two weeks to be implemented There fore 1 day learning periods are recommended only for outlets with regular patterns every day of the week 6 7 How a ...

Страница 45: ...0 Note l The amount of activity required to change the state frommonitor 1 to ready 2 depends on the setting of the activity frequency AF parameter Therefore at the end of day 1 first 24 hours the EMS controller has set all the 30 minutes to ready 2 or saving 0 depending the outlet activity pattern as shown in the following example matrix The EMS controller then continues to run in the ready mode ...

Страница 46: ...ifferential Sd temperature The saving mode temperature is set to ensure that the cooler has sufficient time to lower the product to the ready mode temperature The EMS controller starts lowering the product temperature by the saving restart period Sr before the ready mode starts ensuring that the cooler has sufficient time to reach the ready mode temperature from the saving mode temperature However...

Страница 47: ...nutes Whist in the saving mode the EMS controller must look ahead in the self learning matrix for a ready period by the time defined by the saving restart period Sr For example the EMS controller looks 2 hours ahead If the EMS controller detects an ready period the EMS controller starts to lower the product tem perature as shown below The EMS controller switches to the saving mode if there are no ...

Страница 48: ... serving temperature by keeping the product temperature within the range defined by set point SP parameter and the differential dIF parameter The EMS controller runs the compressor until the set point SP temperature is reached The com pressor is then stopped until the measured temperature reaches the set point SP plus differential dIF temperature During the ready mode EMS controllers display appli...

Страница 49: ...s follows l If a ready period 2 does not have the minimumnumber of door openings or motion counts the EMS controller sets the period to monitor 1 The EMS controller runs in the ready mode for periods set to monitor l If a monitored period 1 does not have the minimumnumber of door openings or motion counts the EMS con troller sets the period to saving 0 Otherwise the EMS controller sets the period ...

Страница 50: ...for safety extra low voltage SELV Therefore if the sensor cable needs to be joined during production or maintenance only connectors normally used in SELV circuits can be used Caution l Connectors designed to carry mains voltages must not be used to join cables to the sensor circuit The temperature sensors have a negative temperature coefficient NTC Each make and type of sensor has a specific resis...

Страница 51: ...n drawn over the products The return air provides a close approximation of the product temperature To measure the return air temperature secure the sensor to allow air to flow over the sensor head The sensor head should be placed at a right angle to the air flow and secured using a P clip The sensor head should not be completely covered by the P clip or the sensor will not function cor rectly Caut...

Страница 52: ...ple fix using a metal pipe clip or direct fitting as shown below Elstat can supply pipe clips for 6 8mm and 8 10mm pipes Caution l Do not use cable ties The head of the sensor is fragile and can be easily damaged Using cable ties to secure the sensor head or sensor cable invalidates the warranty l Do not attach sensor cables to hot pipes or allow the sensor cables to come into contact with hot pip...

Страница 53: ...ler 7 6 Door switch Door switches are used to detect door openings Door switches are SELV safety extra low voltage components that are able to create an open and closed circuit The enhanced door switch and activator are SELV safety extra low voltage components over moul ded for strengthened physical protection and resistance to water ingress and create an open and closed circuit Door switches must...

Страница 54: ... the gap z dimension is correct Z Gap 0mm 0in to 5mm 0 2in 2mm 0 07in The diagram below shows the horizontal vertical and gap alignment between the door switch and the activator for open and closed doors For best results Elstat recommends that enhanced door switches are used with enhanced door switch activators Performance will not be guaranteed if l Enhanced activators are paired with current doo...

Страница 55: ...shows two door switches connected in series 7 9 Motion sensor ems75sz The motion sensor is a passive infra red PIR motion detector and is available integrated into the Controller Display Module or remote to the Controller Display Module as shown in the examples below Integrated motion sensor as shown below Remote motion sensor as shown below As the motion sensor cannot monitor activity through gla...

Страница 56: ...r foamed into place as required by the OEM or installer 7 11 How to mount a remote motion sensor The motion sensor should be mounted vertically with the connector at the bottom for optimal per formance Mounting horizontally with the connector at the sides results in the motion sensor being less sensitive However the motion sensor still works correctly The motion sensor must not be located behind a...

Страница 57: ...a maximum torque of 0 5Nm 0 37lbfft Caution Using rivets invalidates the warranty The dimensions and drilling details of the motion sensor are shown below The dimensions of the mounting holes are shown below 56 of 86 27 February 2014 ...

Страница 58: ...nsor PF3 display alternates between PF3 and the appliance sensor temperature l See How to troubleshoot temperature sensor alarms on page 63 Motion detection LED flashing continuously Motion sensor problem l See How to troubleshoot motion sensor alarms on page 61 Cooler not cooling l See How to troubleshoot not cooling problems on page 61 Cooler lights do not switch on If the EMS controller is in t...

Страница 59: ... CO2 coolers and the ems55advanced CO2 see CO2 alarms for more information For information about the condenser high temperature Ht parameter l See Condenser high temperature Ht on page 70 Follow the chart to troubleshoot condenser high temperature Ht alarms 8 4 Door open alarm display The EMS controller displays dO to show that the cooler door is open However if the door remains open for the durat...

Страница 60: ... triggered if the cooler door is left open for longer than the time defined by the alarm delay Ad parameter If the door is closed and a door open alarm is registered this may indicate problems with the cooler door or the door switch For information about the alarm delay Ad parameter l See Alarmdelay Ad on page 76 Follow the chart to troubleshoot door open alarms on coolers with a door switch 8 6 H...

Страница 61: ...ithout a door switch fitted 8 7 How to troubleshoot problems with freeze up protection 888 Problems with freeze up protection may occur if the ambient temperature falls below 0 C 32 F or if the appliance sensor fails For information about the freeze up protection dtt parameter l See Freeze up protection dtt on page 69 60 of 86 27 February 2014 ...

Страница 62: ...r settings are incorrect Note l The EMS controller stays in the ready mode if the motion detection LED is flashing continuously For information about the motion sensor enable Sn parameter l See Motion sensor enable Sn on page 77 Follow the chart to troubleshoot problems with the motion sensor 8 9 How to troubleshoot not cooling problems Follow the chart below to troubleshoot problems of the cooler...

Страница 63: ...fined by the compressor runtime Ct parameter For information about the set point and compressor run time parameters l See Refrigeration systemfailure Ct on page 72 l See Set point SPC or SPF on page 67 Follow the chart to troubleshoot refrigeration system failure 8 11 Sensor failure Follow the chart to troubleshoot problems with the temperature sensors 62 of 86 27 February 2014 ...

Страница 64: ...lt corrected l PF2 alarms EMS controllers continue running the compressor EMS controllers alternate the display between PF2and the appliance sensor temperature indicating a fault l PF3 alarms EMS controllers continue to run the compressor normally and alternate the display PF3 and the appliance sensor temperature Sensor faults may also be identified by using the input test within the test routine ...

Страница 65: ...64 of 86 27 February 2014 ...

Страница 66: ...l dIF Saving set point SSP and Saving differential Sd Saving restart Sr Design OEMs Defrost method dF and if applicable Defrost termination method dtF Defrost interval dE and Defrost duration dd Defrost activation temperature ddt and Defrost termination temperature dtd Defrost heater dHr Compressor rest time rt Fan cycle on FCO and Fan cycle off FCF Calibration 1 CA1 and Calibration 2 CA2 Uninterr...

Страница 67: ...arameters have been added to the GDC firmware l Sensor enable Sn l Marketing mode Ar Note l The above applies to ems55advanced controllers manufactured after July 2012 Revisions have been made to the Ar parameter for selected controllers during 2014 The following controllers have the enhanced functionality l ems25Plus l ems25Plus CO2 l ems25 CO2 CQC Please refer to controller user manual for furth...

Страница 68: ...C or 01 F Global default 00 C 9 5 Set point SPC or SPF The table below details the set point SPC or SPF parameter Display Description Defines the compressor cut out temperature during the ready mode The set point SP temperature is the lowest measured temperature under normal operating conditions The set point is displayed as SPC set point Celsius or SPF set point Fahren heit depending on whether t...

Страница 69: ...derations Applied to all temperatures measured on the appliance sensor Range 9 9 to 9 9 C 18 to 18 F 9 9 to 4 0 C 18 to 18 F ems55advanced UFF d42 firmware only Global default 0 0 C 0 F 9 8 Calibration 2 CA2 The table below details the calibration CA2 parameter Display Description Calibrates or adds an offset to temperatures measured by the evaporator sensor The offset helps the positioning of the...

Страница 70: ...re during the saving mode Considerations If the saving differential Sd is set too low for example less than 2 0 C the compressor may cycle on the minimum compressor rest time rt Range 0 0 to 9 9 C 0 to 18 F Global default 4 0 C 7 F ems75sz 3 0 C 5 F 9 11 Freeze up protection dtt The table below details the freeze up protection dtt parameter Display Description Defines the temperature to stop furth...

Страница 71: ...enser sensor On reaching the condenser high temperature Ht the EMS controller disables the compressor and activates an alarm Considerations 1 Is not used with CO2 R744 coolers 2 Requires a condenser sensor 3 To set the condenser high temperature Ht measure the refrigeration systemtemperature when the condenser is 75 blocked 4 To disable set below 50ºC or 122ºF Range 0 0 to 125ºC 32 to 257ºF Global...

Страница 72: ...o 86ºF ems75sz 5 to 22ºC 23 to 71ºF Global default 9 0ºC 48ºF OFC firmware 10 0 C 50 F Firmware excluding OFC and SZ 15 0ºC 59ºF SZ firmware 9 16 Compressor rest time rt The table below details the compressor rest time rt parameter Display Description Defines the minimum time between compressor cycles The compressor rest time ensures that the pressures in the refrigeration sys tem have time to equ...

Страница 73: ...only take affect once Delay to saving dS has completed Range 0 to 120 minutes Global default 00 no delay 9 19 Saving restart period Sr The table below details the saving restart period Sr parameter Display Description Cooler runs at the ready mode temperature for the duration of this period to ensure that the cooler is at the set point prior to retail outlet opening time Considerations l Set and v...

Страница 74: ... and beginning of the next defrost cycle A time based defrost cycle helps improve evaporator efficiency Considerations l In the event of power loss the defrost duration dE is not maintained The defrost intervalis reset l If icing up occurs review the values of the defrost parameters Range 0 to 199 hours Global default 06 hours 9 22 Defrost duration dd The table below details the defrost duration d...

Страница 75: ...to use the defrost duration dd or the defrost termination temperature dtd the EMS controller ends the defrost cycle on the first to occur Considerations Defrost method dF must be set to 0 Available only with the ems55 series using OFC Open Front Cooler firmware and the ems75sz Range 00 time dd or 01 time dd or temperature dtd Global default 01 time or temperature 9 25 Fan cycle on FCO The table be...

Страница 76: ... Increasing the value for the display stability d2 slows the rate of change of the displayed temperature Considerations Use the global default value for normal operation Range 1 to 254 Global default 2 9 28 Buzzer enable b0 The table below detail the buzzer enable b0 parameter Display Description Enables or disables a warning buzzer for alarm conditions Door open alarms always sound the warning bu...

Страница 77: ...on Defines the maximum time the cooler door can be open before sounding the alarm buzzer Considerations If disabled the door switch is also disabled The EMS controller does not detect door openings therefore the EMS con troller does not l update the self learning matrix for door activity l manage the evaporator fan management for door activity l sound door alarms if the door is left open Range 00 ...

Страница 78: ... hour period to determine the activity frequency before starting the 1 day or 7 day learning period 9 32 Motion sensor enable Sn The table below details the motion sensor enable Sn parameter Display Description Enables the input from the motion sensor Considerations Must be disabled if a motion sensor is not fitted Range 00 disabled or 01 enabled Global default 01 enabled 9 33 Saving temperature d...

Страница 79: ...or 01 temperature Global default 01 temperature 9 36 Marketing mode Ar The table below details the marketing mode Ar parameter Display Description Sets the cooler lights to remain on at all times for display purposes The coolers lights will remain on during saving mode Considerations Does not affect saving temperature Only applies to the following controllers l ems55advanced and ems55Radvanced GDC...

Страница 80: ...defrost heater during the defrost cycle and do not run the evaporator fan The evaporator fan then remains off for one minute after the end of the defrost cycle 04 Switch on the defrost heater during the defrost cycle and do not run the evaporator fan The evaporator fan then remains off for two minutes after the end of the defrost cycle 05 Switch on the defrost heater during the defrost cycle and d...

Страница 81: ...lue Black P P White Black P P Red Blue P P Green Blue P P Pure Green Blue P P Blue Blue P P White Blue P P Red Green P P Green Green P P Pure Green Green P P Blue Green P P White Green P P Red Red P P Green Red P P Pure Green Red P P Blue Red P P White Red P P Red Silver P P Green Silver P P Pure Green Silver P P Blue Silver P P White Silver P P Red Yellow P P Green Yellow P P Pure Green Yellow P ...

Страница 82: ...10 1 Examples of CDM colours 81 of 86 27 February 2014 ...

Страница 83: ...0 120VAC and 220 240VAC 50 60Hz Compressor 10 10 A p f 0 6 Light 4 4 A p f 0 6 Evaporator fan 6 6 A p f 0 6 Auxiliary 6 6 A p f 0 6 relay used for defrost functionality 11 3 Temperature sensors Sensor Input range oC Input range oF Appliance sensor 10oC to 23 3oC 14oF to 74oF 82 of 86 27 February 2014 ...

Страница 84: ...l Power supply module PSM IPX5 Maximumambient temperature 50oC 122oF 11 5 Product approvals EN60730 1 EN60730 2 9 European Norms ElectricalCertification IEC60730 1 IEC60730 2 9 Glow wire IEC60335 1 InternationalElectrotechnicalCommission Please note CE Conformité Européene European Conformity Replaces RoHS Restriction of Hazardous Substances On controller labelling as of January 2013 83 of 86 27 F...

Страница 85: ...exceed ELVunder normalconditions and under single fault conditions including earth faults in other circuits Safety Extra Low Voltage as described in BS EN 60335 Household and similar electricalappliances Safety standards IEC International Electrotechnical Commission Publisher of internationalstandards for allelectrical electronic and related technologies IP Ingress Protection Aprotection rating ac...

Страница 86: ...e it can detect motion allowing the con troller to be installed out of sight Firmware The code written into the EMS microcontroller containing the rules and algorithms of operation Every controller contains firmware and the version of firmware is identified during power up by two three digit numbers Checksum The checksumis a sum which identifies which parameter set or XMLfile has been loaded onto ...

Страница 87: ...Elstat Electronics Astra Business Centre Roman Way Preston PR2 5AP United Kingdom 44 0 161 22 77 200 www elstatgroup com ...

Отзывы: