No.
Parameter
Please see:
Notes:
18
See "Defrost interval (dE)" on page 73
19
See "Defrost duration (dd)" on page 73
20
See "Defrost method (dF)" on page 73
21
See "Defrost termination method (dtF)"
on page 74
22
See "Fan cycle on (FCO)" on page 74
23
See "Fan cycle off (FCF)" on page 74
24
See "Display stability (d2)" on page 75
25
See "Buzzer enable (b0)" on page 75
26
See "Buzzer duration (b1)" on page 76
27
See "Alarm delay (Ad)" on page 76
28
See "Activity frequency (AF)" on page 76
29
See "Motion sensor enable (Sn)" on page
77
30
See "Saving temperature disable (PEr)"
on page 77
31
See "Learning period (LP)" on page 77
32
See "Display (dIS)" on page 78
33
See "Marketing mode (Ar)" on page 78
34
See "Defrost heater (dHr)" on page 78
Sub-zero exclusive parameter
4.8
How to run the test routine (tst)
The test routine tests the following:
l
All load relays
l
Analogue inputs (temperature sensors and door switch)
l
Motion sensor.
Should a problem be suspected with the ems, it is recommended that the test routine is carried out
before disconnecting or replacing the EMS controller. The test routine can detect any loose or dis-
connected cables and check that the EMS is connected properly to the lights, fan and compressor.
23 of 86
27 February 2014