Defines the maximum continuous runtime of the compressor without reach-
ing the set point (
S P
) temperature.
If the set point (
S P
) temperature is not reached within this time, the EMS con-
troller switches off the compressor and activates the refrigeration system
(
rS F
) alarm.
Considerations
None
Range
00 to 100 hours
Global default
72 hours
9.21
Defrost interval (dE)
The table below details the defrost interval (
dE
) parameter.
Display
Description
Defines the period between the end of defrost cycle and beginning of the next
defrost cycle. A time-based defrost cycle helps improve evaporator efficiency.
Considerations
l
In the event of power loss, the defrost duration (
dE
) is not maintained. The defrost
interval is reset.
l
If icing up occurs, review the values of the defrost parameters.
Range
0 to 199 hours
Global default
06 hours
9.22
Defrost duration (dd)
The table below details the defrost duration (
dd
) parameter.
Display
Description
Defines the maximum time of a defrost cycle.
Considerations
If icing up occurs, review the values of the defrost parameters.
Range
1 to 199 minutes
Global default
15 minutes
9.23
Defrost method (dF)
The table below details the defrost method (
dF
) parameter.