25
Setting parameters
KNX TH65-AP thermal hygrometer
• Version: 27.01.2020 • Technical changes and errors excepted.
Configure a block for the humidity control using the blocking object.
Controller setpoint
If the setpoint is set via parameters:
Set the setpoint for humidity.
If the setpoint is set via communication object:
A starting setpoint is defined as well as a range in which the setpoint may vary.
In "Humidification and dehumidification" control mode, a dead zone is specified so that
no direct changeover switching between humidification and dehumidification is
possible.
Humidification starts when the relative air humidity is below or equal to the setpoint -
dead zone value.
Behaviour of the blocking object with value
• 1 = Block | 0 = release
• 0 = block | 1 = release
Blocking object value
before first call
0 • 1
Specified setpoint using
Parameter • Communication object
Specified setpoint using
Parameter
Setpoint in %
0 … 100
Specified setpoint using
Communication object
The last communicated value
should
• not be retained
• be retained after power restoration
• be retained after power restoration and
programming (not to be used for
first commissioning)
Start setpoint in %
valid until first call
(only if the last retained value is "not"
retained, or retained "after power restora-
tion")
0 … 100
Type of setpoint change
• Absolute value
• Increase / Decrease
Interval
(only when "increasing/decreasing")
0.1°C • 0.2°C • 0.3°C • 0.4°C • 0.5°C • 1°C •
2°C • 3°C • 4°C • 5°C
Dead zone between humidification and
dehumidification in %
(only if both humidification and dehumidifi-
cation are used)
0…50; 10