13
Setting parameters
KNX TH65-AP thermal hygrometer
• Version: 27.01.2020 • Technical changes and errors excepted.
6.
Setting parameters
6.1.
Behaviour on power failure/ restoration of
power
Behaviour following a failure of the bus power supply:
The device sends nothing.
Behaviour on bus restoration of power and following programming or reset:
The device sends all outputs according to their send behaviour set in the parameters
with the delays established in the "General settings" parameter block.
6.2.
General settings
Since the application is used for several devices, the first settings are device-specific.
Please ensure that the following settings are selected for the
KNX TH65-AP
Set the basic data transfer characteristics and select whether or not malfunction ob-
jects should be sent.
6.3.
Measured values: Temperature, humidity
The settings options for temperature and readings are the same.
Use parameters and objects for
the humidity sensor
Yes
Type of logic
Logic for temperature and humidity
sensor
Use parameters and objects for
display
No
Send delays after power-up and programming for:
Readings
5 s • ... • 2 h
Threshold values and switching outputs
5 s • ... • 2 h
Setpoints and control variables
5 s • ... 2 h; 10 s
Logic outputs
5 s • ... 2 h; 10 s
Maximum message rate
• 1 message per second
• ...
• 5 messages per second
• ...
• 20 messages per second
Use malfunction object
No • Yes