If switching occurs by means of a dead zone, cooling control starts at current temper-
ature >= se dead zone
Controller setpoint
The setpoint may be adjusted via parameters or communication objects.
If the setpoint is set via parameters:
Set the setpoint for heating and/or cooling.
If the setpoint is set via communication object:
A starting setpoint value is defined as well as a temperature range in which the setpoint
value may be changed.
Specified setpoint using
Parameter • Communication object
Specified setpoint using
Parameter
Setpoint (heating) in 0.1°C
-300 … 800
Setpoint (cooling) in 0.1°C
-300 … 800
Specified setpoint using
Communication object
The last communicated value should
• not be retained
• be retained after power restoration
• be retained after power restoration and
programming (not to be used for first
commissioning)
Start setpoint (heating) in 0.1°C
valid until first call
(only if the last retained value is "not"
retained, or retained "after power restora-
tion")
-300 … 800; 200
Object value limit (min) in 0.1°C
-300 … 800; 140
Object value limit (max) in 0.1°C
-300 … 800; 250
Start setpoint (cooling) in 0.1°C
valid until first call
(only if the last retained value is "not"
retained, or retained "after power restora-
tion")
-300 … 800; 200
Object value limit (min) in 0.1°C
-300 … 800; 140
Object value limit (max) in 0.1°C
-300 … 800; 250
Type of setpoint change
• Absolute value
• Increase / Decrease
Interval
(only when "increasing/decreasing")
0.1°C • 0.2°C • 0.3°C • 0.4°C • 0.5°C • 1°C •
2°C • 3°C • 4°C • 5°C